sinee — Руководство по эксплуатации SINEE EM760 — высокоэффективный инвертор (EN)

User’s Guide for EM760 series high-performance vector inverter RUN 24V 正/反转 RUN Operation 运行 F/R 变频器 Inverter Forward/reverse F/R Xi Xi Parking 停车 Output frequency 输出 频率 f COM -f 时间 Time (a) Wiring diagram of three-line control (F00.03=3) (d) F04.19=0, F00.03=3: forward/reverse running logic Fig. 5-3 Three-line Control 5.6 Common Process Parameters of Inverter Note: Common process parameters may also include the input and output terminal function settings. Refer to the F02 and F03 groups in the function table. 5.7 Motor Parameter Identification For the better control performance, motor parameters must be identified.

38 Function Default Attrib Function code name Parameter description Unit code setting ute F00.01 Drive control mode of motor 1 0: V/F control (VVF) 1: Speed sensorless vector control (SVC) 2: Speed sensor vector control (FVC) 0  F00.04 Options of main frequency source A 0: digital frequency setting F00.07 1: AI1 2: AI2 3: AI3 4: AI4 (expansion card) 5: high frequency pulse input (X7) 6: Percentage setting of main frequency communication 7: Direct setting of main frequency communication 8:

digital potentiometer setting 0  F00.07 Digital frequency setting 0.00 to maximum frequency F00.16 Hz 0.00 ● F00.14 Acceleration time 1 0.00~650.00 (F15.13=0) s 15.00 ● F00.15 Deceleration time 1 0.00~650.00 (F15.13=0) s 15.00 ● F00.16 Maximum frequency 1.00~600.00 Hz 50.00  F00.18 Upper frequency limit Lower frequency limit F00.19 to maximum frequency F00.16 Hz 50.00 ● F00.19 Lower frequency limit 0.00 to upper frequency limit F00.18 Hz 0.00 ● F00.21 Reverse control 0: Allow forward/reverse running 1:

Prohibit reversing 0  Identification Method Application Identification Effect F01.34=1 Static self-learning of asynchronous motor It is applied where the motor and load cannot be separated easily and rotary self-learning is not allowed. General F01.34=11