User’s Guide for EM760 series high-performance vector inverter 76 F09.36 Upper limit of feedback voltage 0.00 to upper limit of feedback voltage V 0.00 ● F09.37 Options of integral action within the set change time of PID 0: Always calculate the integral term 1: Calculate the integral term after the F09.21 set time is reached 2: Calculate the integral term when the error is less than F09.38 0 ● F09.38 Input deviation of integral action within the set change time of PID 0.00~100.00 % 30 ● F09.39 Wake-up option 0: target pressure F09.01* coefficient of wake-up action point 1:
Wake-up action point (F09.30) 0 F09.40 Coefficient of wake-up action point 0.0-100.0 (100% corresponds to PID setting) % 90.0 ● F09.41 Pipeline network alarm overpressure 0.0 to pressure sensor range F09.03 bar 6.0 ● F09.42 Overpressure protection time 0-3600 (0: invalid) s 0 ● F09.43 PID reverse limit 0: Invalid 1: valid 0 F10 Communication function group F10.00 Local Modbus communication address 1-247; 0: broadcast address 1 F10.01 Baud rate of Modbus communication 0: 4800 3: 38400 1: 9600 4: 57600 2: 19200 5: 115200 1 F10.02 Modbus data format 0: 1-8-N-1 (1 start bit + 8 data bits + 1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity check bit + 1 stop bit) 2:
1-8-O-1 (1 start bit + 8 data bits + 1 odd parity check bit + 1 stop bit) 3: 1-8-N-2 (1 start bit + 8 data bits + 2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity check bit + 2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity check bit + 2 stop bits) 0 F10.03 Communication timeout 0.0s-60.0s; 0.0: invalid (valid for the master-slave mode) s 0.0 ● F10.04 Modbus response delay 1~20 ms 2 ● F10.05 Options of master-slave communication function 0: Invalid 1: valid 0 F10.06 Master-slave options 0: slave 1: Host (broadcast transmission) 0 F10.07 Data sent by host 0: output frequency3: set torque 1