EMC filters 3-line filters for converters and power electronics Series/Type: B84143B/K*S080/S081 Date: May 2014 © EPCOS AG 2015. Reproduction, publication and dissemination of this publication, enclosures hereto and the information contained therein without EPCOS' prior express consent is prohibited. EPCOS AG is a TDK Group Company.
Cover
3-line filters B84143B/K*S080/S081 for converters and power electronics Power line filters for 3-phase systems Rated voltage V R : 520/300 V AC and 760/440 V AC Rated current I R :
180 A to 1600 A Construction 3-line filters Metal case Versions B84143B*S080 type for standard applications B84143B*S081 type for applications with higher voltages B84143K*S081 type without Y capacitors, very low leakage current Features Optimized leakage current Easy to install Very compact design Optimized for operation under full load Low weight Design complies with IEC 60939 UL and cUL approval Typical applications Frequency converters for motor drives Photovoltaics Wind farms Terminals Power supplies Busbars Marking Marking on component: Manufacturer's logo, ordering code, rated voltage, rated current, rated temperature, climatic category, date code, approvals Minimum data on packaging:
Manufacturer's logo, ordering code, quantity, date code Accessories For busbar filter series B84143B/K*S080/S081 protective covers can be supplied as accessories. See chapter "Accessories" B84143Q*S080. Page 2 of 16 Please read Cautions and warnings and Important notes at the end of this document.
Cover
3-line filters B84143B/K*S080/S081 for converters and power electronics Typical circuit diagrams B84143B*S08* B84143K*S081 Page 3 of 16 Please read Cautions and warnings and Important notes at the end of this document.
Cover
3-line filters B84143B/K*S080/S081 for converters and power electronics Technical data and measuring conditions Characteristics and ordering codes Ч = Approval granted: Type *S080 for 500/290 V Type *S081 for 600/350 V Page 4 of 16 Please read Cautions and warnings and Important notes at the end of this document. Rated voltage V R Type S080: 520/300 V AC (50/60 Hz) Type S081: 760/440 V AC (50/60 Hz) Rated voltage for IT mains supply Type S081: 560/320 V AC (50/60 Hz) See also chapter "General technical information", section 7. Rated current I R Referred to 40 °C rated temperature (250 A ...
1600 A) Referred to 60 °C rated temperature (180 A) Rated peak withstand current I pk According IEC 60439-1:2011, chapter 3.8.10.2; limited by I2t characteristics of fuse Test voltage V test Type S080: 2240 V DC, 2 s (line/line) 2720 V DC, 2 s (lines/case) Type S081: 3270 V DC, 2 s (line/line) 2890 V DC, 2 s (lines/case) Overload capability (thermal) 1.5 I for 3 min per hour or R 2.5 I for 30 s per hour R Leakage current l LK At V and 50 Hz R Climatic category (IEC 60068-1) 25/100/21 (25 °C/+100 °C/21 days damp heat test) Approvals UL 1283; CSA C22.2 No.8 (Type *S080: 500/290 V; Type *S081: 600/350 V) I R A I pk kA I LK mA R typ mΩ Approx.
weight kg Ordering code Approvals V = 520/300 V AC R 180 250 320 400 600 1000 1250 1600 25 25 50 50 50 75 75 75 14 14 14 14 14 14 14 14 0.110 0.110 0.051 0.048 0.043 0.029 0.022 0.022 5.0 5.0 7.2 7.5 7.8 18.5 24.5 24.5 B84143B0180S080 B84143B0250S080 B84143B0320S080 B84143B0400S080 B84143B0600S080 B84143B1000S080 B84143B1250S080 B84143B1600S080 × × × × × × × × × × × × × × × ×