Downloaded from https://www.everyspec.com MIL-HDBK-704-3 METHOD TAC107 Total Voltage Distortion POWER GROUP: Three Phase, 400 Hz, 115 V AIRCRAFT ELECTRICAL OPERATING CONDITION: Normal PARAMETER: Total Voltage Distortion 1. Scope. 1.1 Purpose. This test procedure is used to verify that three phase, 115 Volt, 400 Hz power utilization equipment operates and maintains specified performance when subjected to voltage waveforms having a distortion factor as specified by the applicable edition(s) of MIL-STD-704. 2. Validation criteria.
The utilization equipment is considered to have passed if the utilization equipment operates and maintains performance as specified in the utilization equipment performance specification document for normal aircraft electrical conditions when subjected to voltage waveforms having a distortion factor as specified by the applicable edition(s) of MIL- STD-704 and as noted in table TAC107-I. The utilization equipment must maintain specified performance for a length of time that confirms the utilization equipment can operate continuously when subjected to distorted voltage waveforms and should be, not less than thirty (30) minutes.
The utilization equipment must not suffer damage or cause an unsafe condition. TABLE TAC107-I. MIL-STD-704 limits for total voltage distortion. 3. Apparatus. The test equipment should be as follows: a. Programmable AC power supply b. True RMS voltmeter c. Frequency counter d. Spectrum analyzer e. Distortion meter 4. Test setup. Configure the test setup as shown in figure TAC107-1. Measurements, except current, must be made within 10 cm of the input power terminals of the UUT. 4.1 Calibration. Install a resistive load in the test setup shown in figure TAC107-1 in place of the UUT. The resistive load should be sized to draw the same current as the UUT.
Set 39 Limit 704A 704B 704C 704D 704E 704F Voltage Distortion Factor 0.08 0.05 0.05 0.05 0.05 0.05