Downloaded from https://www.everyspec.com MIL-HDBK-802 (SH) 2 July 1990 6.3.4.1 Four-cable connection with endwavs approach to edgewise terminals. We will connect a four, single-conductor cable run approaching endways to edgewise terminals in accordance with figure 52. NOTES: 1. The cable run will approach the terminals with its axis in the line with the horizontal axis of the center terminal, T2. The two cables 1 and 3, which lie in a horizontal plane, will be bolted to the opposite sides of terminal T2. Cable 2 will be bent to the left and slightly down to connect to terminal 2. 3. T1. Cable 4 will be bent to the right and slightly up to connect to terminal T3.

The area outlined by cables 1 and 4 equals the area of the cable run outlined by cables 2 and 3. The polarity of the current in the loop made by cables 1 and 4 is opposite to the polarity of the current in the loop made by cables 2 and 4. 5. 3. FIGURE 52. Connection of an endways cable run with four cables to edgewise terminals. 6.3.4.2 Four-cable connection with crossways approach to edgewise terminals. We will connect a four, single-conductor cable run approaching crossways to edgewise terminals in accordance with figure 53. 93