Downloaded from https://www.everyspec.com MIL-HDBK-802( SH) 2 July 1990 This arrangement will create current loops of equal area and opposite polarity, causing the stray magnetic field to be small. A simple modification of the above procedure can accommodate a sideways cable run. 6.4 Disconnect switch boxes and contactor panels. We will consider here the design of disconnect switch boxes and contactor panels that may be connected in a magnetic minesweep cable run between a magnetic minesweep generator and a mine- sweep cable terminal box.
The design considerations may also be applied to other control equipment used in dc power circuits such as switchboards, power panels and motor controllers. The arrangement of conductors and devices for disconnect switch and contactor panels will be in accordance with 6.4.1 through 6.4.12.4. 6.4.1 Basic conductor arrangement. The basic arrangement of conductors in disconnect switch boxes, contactor panels, switchboards, power panels and motor controllers will be a central conductor carrying two units of current in one direction sandwiched between two symmetrically placed conductors each carrying one unit of current in the opposite direction (see figure 60).
The basic conductor arrangement is compatible with the three-terminal arrangements for magnetic minesweep quad cable runs in accordance with 6.3.4. NOTE: In all figures, quantity of arrows indicates relative magnitude of current. The direction of the l rrwa indicates direction of current. FIGURE 60. Basic arrangement of conductors in disconnect switch boxes and contactor panels. 101