Downloaded from https://www.everyspec.com 6.4 8.2.1 Single-pole contactor. We do not discuss single-pole contractors because if a single-pole contactor is used, it will be put in the center conductor and the two outer conductors will be shaped to simulate the other two poles of a three-pole contactor. 6.4.9 Flexibility of folded arrangement. If we look at a folded dlsconnect switch box from the side (see figure 67), the conductors in the box will look like the three sides of a rectangle shown to the right of the terminals T. On figure 67 each T indicates three terminals in a line perpendicular to the plane of the paper so that only one is visible.

We see in 6.3.4.1 that cable runs approaching and leaving the box in any of the directions shown can be readily connected to the three terminals. Furthermore, the incoming and outgoing cable runs do not have to be either horizontal or vertical but can be at any angle. In addition, all of the arrangements can be rotated through 90 degrees (or any other angle) in the plans of the figure so that there is a considerable degree of flexibility in connecting the folded arrangement to cable runs. For this reason it is considered unlikely that there will be any need for anything but the folded arrangement of disconnect switch boxes or contactor panels.

The only exception would appear to be in the case of special circumstances, which are considered in 6.4.10. FIGURE 67. Various ways in which cable runs can be connected to a folded disconnect switch. 6.4.10 The crisscross arrangement In the folded arrangement we will have the connections to the terminals for the incoming and outgoing cable runs at the same end of the disconnect switch box or contactor panel In some cases that will be an advantage. In other cases it will be of no particular disadvantage because of the flexibility in connecting cable runs to the folded arrangement.

There may also be cases, however, in which special circumstances make it indispensable or highly advantageous to have a disconnect switch box or contactor panel with incoming and outgoing terminals at opposite ends In such cases, but only in such cases, the crissscross arrangement may be used 110