Перечни параметров Руководство по программированию привода VLT ® HVAC Basic Drive 5.1.2 0-** Управление и отображение 5 5 Таблица 5.3 5.1.3 1-** Нагрузка/двигатель 100 MG18B250 - VLT ® является зарегистрированным товарным знаком Danfoss Par. No.
# Parameter description Default value 2-set-up Change during operation Conver- sion index Type 0-0* Basic Settings 0-01 Language [0] English 1 set-up TRUE - Uint8 0-03 Regional Settings ExpressionLimit 1 set-up FALSE - Uint8 0-04 Operating State at Power-up [0] Resume All set-ups TRUE - Uint8 0-06 GridType ExpressionLimit 1 set-up FALSE - Uint8 0-07 Auto DC Braking IT [0] Off 1 set-up FALSE - Uint8 0-1* Set-up Operations 0-10 Active Set-up [1] Set-up 1 1 set-up TRUE - Uint8 0-11 Programming Set-up [9] Active Set-up 1 set-up TRUE - Uint8 0-12 Link Setups [20] Linked All set-ups FALSE - Uint8 0-3* LCP Custom Readout 0-30 Custom Readout Unit [1] % 1 set-up TRUE - Uint8 0-31 Custom Readout Min Value 0.0 CustomReadoutUnit 1 set-up TRUE -2 Int32 0-32 Custom Readout Max Value 100.0 CustomReadoutUnit 1 set-up TRUE -2 Int32 0-37 Display Text 1 0 N/A 1 set-up TRUE 0 VisStr[21] 0-38 Display Text 2 0 N/A 1 set-up TRUE 0 VisStr[26] 0-39 Display Text 3 0 N/A 1 set-up TRUE 0 VisStr[26] 0-4* LCP Keypad 0-40 [Hand on] Key on LCP [1] Enable All All set-ups TRUE - Uint8 0-42 [Auto on] Key on LCP [1] Enable All All set-ups TRUE - Uint8 0-44 [Off / Reset] Key on LCP [1] Enable All All set-ups TRUE - Uint8 0-5* Copy/Save 0-50 LCP Copy [0] No copy 1 set-up FALSE - Uint8 0-51 Set-up Copy [0] No copy 1 set-up FALSE - Uint8 0-6* Password 0-60 Main Menu Password 0 N/A 1 set-up TRUE 0 Uint16 Par.
No.
# Parameter description Default value 2-set-up Change during operation Conver- sion index Type 1-0* General Settings 1-00 Configuration Mode [0] Open Loop All set-ups TRUE - Uint8 1-01 Motor Control Principle [1] VVC+ All set-ups FALSE - Uint8 1-03 Torque Characteristics [1] Variable Torque All set-ups FALSE - Uint8 1-06 Clockwise Direction [0] Normal All set-ups FALSE - Uint8 1-2* Motor Data 1-20 Motor Power ExpressionLimit All set-ups FALSE - Uint8 1-22 Motor Voltage ExpressionLimit All set-ups FALSE 0 Uint16 1-23 Motor Frequency ExpressionLimit All set-ups FALSE 0 Uint16 1-24 Motor Current ExpressionLimit All set-ups FALSE -2 Uint32 1-25 Motor Nominal Speed ExpressionLimit All set-ups FALSE 67 Uint16 1-26 Motor Cont.
Rated Torque ExpressionLimit Not common set-up FALSE -1 Uint32 1-29 Automatic Motor Adaption (AMA) [0] Off All set-ups FALSE - Uint8 1-3* Adv. Motor Data I