Перечни параметров Руководство по программированию привода VLT ® HVAC Basic Drive 5.1.11 14-** Специальные функции 5 5 Таблица 5.12 MG18B250 - VLT ® является зарегистрированным товарным знаком Danfoss 107 Par. No.
# Parameter description Default value 2-set-up Change during operation Conver- sion index Type 14-0* Inverter Switching 14-01 Switching Frequency ExpressionLimit All set-ups TRUE - Uint8 14-03 Overmodulation [1] On All set-ups FALSE - Uint8 14-08 Damping Gain Factor 96.0% All set-ups TRUE 0 Uint8 14-1* Mains On/Off 14-12 Function at Mains Imbalance [0] Trip 1 set-up TRUE - Uint8 14-2* Reset Functions 14-20 Reset Mode [0] Manual reset All set-ups TRUE - Uint8 14-21 Automatic Restart Time 10.0 s All set-ups TRUE 0 Uint16 14-22 Operation Mode [0] Normal operation All set-ups TRUE - Uint8 14-27 Action At Inverter Fault [1] Warning All set-ups TRUE - Uint8 14-4* Energy Optimising 14-40 VT Level 90% All set-ups FALSE 0 Uint8 14-41 AEO Minimum Magnetisation 66% All set-ups FALSE 0 Uint8 14-5* Environment 14-50 RFI Filter [1] On 1 set-up FALSE - Uint8 14-51 DC-Link Voltage Compensation [1] On All set-ups FALSE - Uint8 14-52 Fan Control [0] Auto 1 set-up TRUE - Uint8 14-53 Fan Monitor [1] Warning 1 set-up TRUE - Uint8 14-55 Output Filter [0] No Filter 1 set-up FALSE - Uint8 14-6* Auto Derate 14-63 Min Switch Frequency 1.0 kHz 1 set-up FALSE 0 Uint16