Параметры Руководство по программированию привода VLT ® HVAC Basic Drive 3 3 MG18B250 - VLT ® является зарегистрированным товарным знаком Danfoss 61 6-92 Terminal 42 Digital Output Опция: Функция: [61] Comparator 1 [62] Comparator 2 [63] Comparator 3 [64] Comparator 4 [65] Comparator 5 [70] Logic rule 0 [71] Logic rule 1 [72] Logic rule 2 [73] Logic rule 3 [74] Logic rule 4 [75] Logic rule 5 [80] SL digital output A [81] SL digital output B [82] SL digital output C [83] SL digital output D [160] No alarm [161] Running reverse [165] Local ref. active [166] Remote ref.
active [167] Start command activ [168] Drive in hand mode [169] Drive in auto mode [193] Sleep Mode [194] Broken Belt Function [196] Fire Mode [198] Drive Bypass 6-94 Terminal 42 Output Max Scale Диапазон: Функция: Current (mA) 20 0/4 0%Analogue Analogue 100%Variable output Output for Min Scale Max Scale output par. 6-93 par. 6-94 example: Power Рисунок 3.12 6-96 Terminal 42 Output Bus Control Диапазон: Функция: 0 * [0 - 16384 ] 6-93 Terminal 42 Output Min Scale Диапазон: Функция: 0 %* [0 - 200 %] Установите масштаб минимального значения выходного аналогового сигнала на клемме 42 (0 или 4 мА).
Задайте значение в виде процента полного диапазона переменной, выбранной в 6-91 Terminal 42 Analog Output. 6-94 Terminal 42 Output Max Scale Диапазон: Функция: 100 %* [0 - 200 %] Установите масштаб максимального выходного значения (20 мА) масштабирования на клемме 42. Задайте значение в виде процента полного диапазона переменной, выбранной в 6-91 Terminal 42 Analog Output.