ABB — 3.3.1. Status word

FIELDBUS COMMUNICATION 3.3. Status word and Control word 3.3.1. Status word The status word register is used to monitor the motor. This register can be used as an alter- native to using the digital input telegram (section 3.1).

Read status word using Modbus function code 3 Read Holding Registers or 4 Read Input Registers Protocol Address Bit Data Description 0300h 0 Reserved 1 Motor stopped status 0 = Motor running 1 = Motor stopped 2 Run status 0 = Motor stopped 1 = Motor running 3 Reserved 4 Reserved 5 Auto mode sta- tus 1 0 = Local control 1 = Modbus master control 6 Fault status 0 = No active fault 1 = One or more active faults 7 Reserved 8 Reserved 9 Reserved 10 Reserved 11 Start status Hardwire DI Start input signal state 0 = DI Start signal inactive 1 = DI Start signal active 12 Stop status Hardwire DI Stop input signal state 0 = DI Stop signal inactive 1 = DI stop signal active 13 Reset status Hardwire DI Reset input signal state 0 = DI Reset signal inactive 1 = DI Reset signal active 14 TOR status 0 = Softstarter is not in top of ramp 1 = Softstarter is in top of ramp (bypass closed) 15 Ready to start status 1 = No faults are active, control supply voltage is stable and motor will start when start command is given 0 = Fault is active or control supply voltage is not sta- ble and motor will not start when start command is given 1) Auto mode reflects the control state of the Softstarter.

This is affected by a combination of: – The Auto mode input signal from the Modbus master (protocol address 0105h in the digi- tal output telegram or bit 5 in the control word). – The parameter “Fieldbus control”. STATUS Approved PAGE 7/22 © Copyright 2019 ABB. All rights reserved. SECURITY LEVEL Public DOCUMENT ID. 1SFC132367M0201 REV. B LANG. en