• When on the operation panel is pressed in the PU operation mode while Pr.551 PU mode operation command source 2 selection = "9999 (initial value)" and the FR-PA07/LU08/PU07 is connected to the PU connector on the inverter, the inverter is stopped and the indication "PS" is displayed on the operation panel. 2 How to restart the inverter which stopped with the push of on the PU in the External operation mode (How to reset the PU stop (PS) fault) 3 • To reset the PU stop fault using the operation panel 1. After completion of deceleration to a stop, switch OFF the STF or STR signal. 2. Press . " " is cleared.
4 (when Pr.79 Operation mode selection = "2 or 3") 5 • To reset the PU stop fault using the FR-PU07/PA07/LU08 1. After completion of deceleration to a stop, switch OFF the STF or STR signal. 2. Press . " " is cleared. 6 EXT 7 Speed Time Operation panel STF ON (STR) OFF 8 Stop/restart example for External operation 9 • The inverter can be restarted by resetting the power supply or resetting with the RES signal. 10 • Even when Pr.250 Stop selection ≠ "9999" and coasting stop is selected, the PU stop function executed in the External operation mode does not provide coasting stop but deceleration stop.
5.3.2 PU display language selection You can switch the display language of the parameter unit (FR-PU07) to another. 5.3.3 Beep control The key operation beep (buzzer) of the LCD operation panel (FR-LU08) or parameter unit can be turned ON/OFF. 87 5. PARAMETERS 5.3 (E) Environment setting parameters NOTE EXT Key Key NOTE Pr. Name Initial value Setting range Description 145 E103 PU display language selection 1 0 Japanese 1 English 2 German 3 French 4 Spanish 5 Italian 6 Swedish 7 Finnish Pr. Name Initial value Setting range Description 990 E104 PU buzzer control 1 0 Beep (buzzer) is OFF. 1 Beep (buzzer) is ON.