Basic software procedures К Log into the iRMC web interface. Executing the fan test via the iRMC web interface The System menu is displayed on default. К Open the Cooling page. К Expand the Cooling Devices group. К Click Start Fan Test I For more information on iRMC settings, see the iRMC user guides. Executing the fan test via ServerView Operations Manager К Open the ServerView Operations Manager and log in. К Under Administration select Server Configuration . К In the hierarchy tree of the Server list tab, select the server to be configured. К In the right-hand side of the window, specify the details on the selected server and confirm your entries by clicking GO... .
In the left-hand section of the window, the Configuration tab is being activated. К In the navigation area of the Configuration tab, select Other Settings . К Under Daily Fan Test , set the daily fan test time to a few minutes from the current time. (Ensure to note down your previous setting.) К Click Save Page . The fan test will be started at the specified time. К After the fan test is complete, restore the time setting to its initial value and click Save Page . In case of maintenance done by Fujitsu engineers in Japan: Executing the fan test via Chassis ID Prom Tool I Please follow the instructions provided separately. RX2530 M4 Upgrade and Maintenance Manual 107