HiPhi — 2016 Guide IEC EN61439 en 98171000 5 2016

Step 2: Design of an assembly and design verification Calculation of the power dissipation (P V) with ENYGUIDE planning software When selecting an enclosure, the power dissipation values for the selected enclosure can be displayed in a new dialog box "power loss". The power loss calculation differentiates between installation de- vices, which have been built-in by the original manufacturer (Hensel) ( 1. ) and those which have been additionally selected by the manu- facturer of the assembly (panel builders) ( 2. ). e a d v a l u e o s u r e + r f o r p o w The feed and the number of ultimate user circuits are preset. The values have to be checked and corrected if necessary.

The device identifi cation is optional. e n c l e r d i s e l e c t s i p a S t i o n 1. 2. Example: Mi isolator box Example: Mi Circuit breaker box Installation devices by HENSEL (original manufacturer) Example: Isolator boxes The built-in devices in enclosures with electrical functions are pre-installed by the original manufacturer (Hensel). 1. 2. Installation devices by the manufacturer of a power switchgear and controlgear assembly Example: Circuit breaker boxes Additionally selected installation devices, which have been selected by the panel builder using the add-to-installation-devices function.

The specifi ed power loss values are reference values and must be checked and corrected if necessary. 28 Individual planning of installation devices Installation devices, which are not listed within the add-to- + installation-device function, can be manually added ( ) or can be deleted ().