omron — 8. Faults and alarms

8. Faults and alarms Note: Refer to user’s manual for full fault code listings EN-22 Fault Display Fault name and meaning Possible cause and remedy OC Overcurrent Output current is higher than 250% of inverter rated current. Check output for shortcircuit or ground fault. The load is too large, reduce it or use larger inverter. Check motor FLA rating compared to inverter and V/f setting. OV Overvoltage DC bus voltage has exceeded detec- tion level. Load inertia is too large and the motor is re- generating. Increase deceleration time (n020 or n022). Connect an external braking resistor and set n092 to 1. Check braking resistor and wiring.

UV1 Main circuit undervoltage DC bus voltage is below detection level. Check mains power supply voltage and con- nections. Check correct supply for inverter be- ing used. Monitor for mains dips or interruptions. OH Unit overheat Temperature inside the inverter has exceeded 110°C Refer to manual for installation guidelines and recommendations. Check cooling fan (if fit- ted). Check V/f characteristic or reduce carrier frequency. OL1 Motor overload The inverter is protecting the motor from overload, based on an internal I2t calculation using n036 setting. Check and reduce the load. Check V/f characteristic (Vmax and Fmax). Increase the running speed of motor.

Increase acceleration/deceleration times. EF External fault An external fault has been input. Check your control terminal wiring. A multi-function digital input has been set to 3 or 4. Run signal has to be removed before this can be reset. SER (flashing) Sequence error Inverter received LOCAL / REMOTE selection command, or communica- tion / control circuit selection com- mand signal during operation. Check sequence and make sure that LOCAL / REMOTE selection or communication / control circuit selection command is not set during op- eration. bb (flashing) External Baseblock An external baseblock command has been input. Check your control terminal wiring.

A multi-function digital input has been set to 12 or 13. EF (flashing) Sequence error Sequence Error has occurred. Forward and reverse run signal have been applied simultaniously. Check sequence and make sure that FORWARD and REVERSE Run is not set at the same time.