3 Electrical Installation ENGLISH „ Control Circuit The control terminal board is equipped with screwless terminals. Always use wires within the specification listed below. For safe wiring it is recommended to use solid wires or flexible wires with ferrules. The stripping length respectively ferrule length should be 8 mm. Wire Type Wire size Solid 0.2 to 1.5 mmІ Flexible 0.2 to 1.0 mmІ Flexible with ferrule 0.25 to 0.5 mmІ ‹ EMC Filter Installation This drive has been tested in accordance with European standards EN61800-3. In order to comply to the EMC standards, wire the main circuit as described below. 1.
Install an appropriate EMC noise filter to the input side.See the list above or refer to the instruction manual for details. 2. Place the drive and EMC noise filter in the same enclosure. 3. Use braided shield cable for the drive and motor wiring 4. Remove any paint or dirt from ground connections for minimal ground impedance 5. Install an AC reactor at drives smaller than 1 kW for compliance with the EN61000-3-2.
Refer to the instruction manual or contact your supplier for details Cable clamp N L1 PE L3 L2 L1 PE Cable clamp Drive Grounding Surface (remove any paint) Cable shield grounding clamp Braid shielded motor cable Ground shield at motor side Cable shield grounding clamp Braid shielded motor cable Ground shield at motor side EMC Standards Compliant Wiring of Single- and Three Phase Units M M I67E-EN V1000 Quick Start Guide 11 P Grounding S (remove any N L1E EMC Filter R/L1S/L2T/L3 Wiring distance as short as possible P anel or mounting wall Metal plate urface paint) U/T1 V/T2 W/T3 Grounding S (remove any N L1E EMC Filter R/L1S/L2T/L3 urface paint) U/T1 V/T2 W/T3 P Grounding S (remove any E L3L2 L1 EMC Filter R/L1S/L2T/L3 P anel or mounting wall Metal plate urface paint) UU//TT11 VV//TT22 WW//TT33 Grounding S (remove any E L3L2 L1 EMC Filter R/L1S/L2T/L3 urface paint) UU//TT11 VV//TT22 WW//TT33 Grounding Surface (remove any paint) Wiring distance as short as possible