6 Parameter Table 24 I67E-EN V1000 Quick Start Guide Par. Name Description Digital Input Settings H1-01 to H1-06 DI S1 to S6 Function Selection Selects the function of terminals S1 to S6. A list of the major functions can be found at the table end. Digital Output Settings H2-01 DO MA/MB Function Set the function for the relay output MA-MB-MC. H2-02 DO P1 Function Sets the function for the photo- coupler output P1. H2-03 DO P2 Function Sets the function for the photo- coupler output P2. Major functions are listed at the end of the table. Analog Input Setting H3-01 A1 Signal Level Sel. 0:0 to +10 V (neg. input is zeroed) 1:0 to +10 V (bipolar input) H3-02 A1 Func- tion Sel.
Assign a function to terminal A1. H3-03 A1 Gain Sets the input value in % at 10 V analog input. H3-04 A1 Bias Sets the input value in % at 0 V analog input. H3-09 A2 Signal Level Selection 0:0 to +10 V (neg. input is zeroed) 1:0 to +10 V (bipolar input) 2:4 to 20 mA (9 bit input) 3:0 to 20 mA H3-10 A2 Func- tion Sel. Assign a function to terminal A2. H3-11 A2 Gain Sets the input value in % at 10 V /20 mA analog input. H3-12 A2 Bias Sets the input value in % at 0 V / 0 mA / 4 mA analog input. Analog Input Setting H4-01 AM Monitor Selection Enter value equal to U1- monitor values. Example: Enter “103” for U1-03. H4-02 AM Gain Sets terminal AM output voltage equal to 100% monitor value.
H4-02 AM Bias Sets terminal AM output voltage equal to 0% monitor value. Par. Name Description Pulse Input Setting (Free. ref. input) H6-02 RP Input Scaling Sets the number of pulses (in Hz) that is equal to 100% input value. H6-03 Pulse Train Input Gain Sets the input value in % at pulse input with H6-02 frequency. H6-04 Pulse Train Input Bias Sets the input value in % at 0 Hz pulse input frequency. Pulse Output Setting H6-06 MP Monitor Sel. Enter value equal to U- monitor values. Example: Enter “102” for U1-02. H6-07 MP Moni- tor Scaling Sets the number of output pulses when the monitor is 100% (in Hz). Motor Overheat Protection L1-01 Motor Overload Prot. Sel.
Sets the motor overload protec- tion. 0:Disabled 1:Standard fan cooled motor 2:Standard blower cooled motor 3:Vector motor L1-02 Motor Overload Prot. Time Sets the motor overload protec- tion time in min. Normally no change is necessary. Stall Prevention L3-01 Stall Prevention Selection during Accelera- tion 0:Disabled - Motor accelerates at active acceleration rate and may stall with too heavy load or too short accel time. 1:General Purpose - Hold acceleration when current is above L3-02. 2:Intelligent - Acceleration in the shortest possible time. L3-02 Stall Prev. Level dur- ing Accel. Sets the current level for stall prevention during acceleration. L3-04 Stall Prev.
Selection during Decel. 0:Disabled - Deceleration as set. OV might occur. 1:General Purpose - Decelera- tion is hold if DC bus voltage rises high.