Tags and the Project Database You can replace one or more tags by clicking the Whole Tag Name tab. Current tags used are displayed. The original tag names are shown in the From column on the left, and you can enter your new tag names in the To column on the right. Whole Tag Name tab Note that this does not rename or delete any tag — it only replaces the tags used in the object with other tags from the database. You can also replace one or more strings (e.g., button captions, descriptive text) by clicking the String Value tab. String Value tab When you are done, click OK .
Removing unused tags from the project database The Remove unused tags tool is used to scan the project database for unused tags, which you can then select and remove. "Unused tags" are tags that you have defined in the project database but have not used in any screen or task worksheet. Since your project has a limited number of available tags (as determined by your product/license type), you may want to remove some or all of these unused tags to decrease your project's tag count. 1. Save and close all open project screens and worksheets. 2. On the Home tab of the ribbon, in the Tags group, click Remove unused tags . InduSoft Web Studio Page 129