Tags and the Project Database 7. Reselect only the POUs and Global Variables that you want to export to IWS. Do not select libraries. With the objects selected, check all of the options at the bottom of the dialog. For example: 8. Click OK to close the Set object attributes dialog, and then click OK again to close the Options window. 9. Choose Project > Rebuild All from the menu bar. The system will rebuild the project, generating a symbol file that contains the desired POUs and Global Variables . IMPORTING FROM PANELMATE PLUS DATABASES Note: This wizard is sold as an add-on and requires a license to be enabled. Consult your software vendor for further information.
This wizard allows you to import not only the tags, but also the screens, alarm configuration and communication interface from a project created with PanelMate Plus ™ software. Using this wizard, you can convert a PanelMate ™ program (developed with PanelMate Plus ™ ) into the IWS format and run it under any platform supported by IWS. • Import Screens : Check this option to import the graphical screens (including their objects and animations) to IWS. • PanelMate Model : Press the Browse button to select the directory where the database files of the PanelMate Plus project that you intend to import are stored. • Application :
After selecting the correct path on the PanelMate Model field, the programs available in this directory will be available in this combo-box. Select the program that you intend to import before pressing the Next button. InduSoft Web Studio Page 145