Screens and Graphics Tip: You are not required to enter the protocol type in the URL field. When you select a protocol type from the Hyperlink Type list, the project automatically adds the protocol's prefix to the URL address. • Disable field: Type a value greater than zero into this field to disable the hyperlink Command animation for the selected object(s). • E-Sign checkbox: When this option is checked, the user will be prompted to enter the Electronic Signature before executing the animation. • Security field: Type a value into this field to specify a security level for the object(s).
If a user logs on but does not have the required security level, the project disables the hyperlink command for the object(s). BARGRAPH ANIMATION On the Graphics tab, in the Animations group, click Bargraph to add bar graph properties to a selected object, then double-click on the object to open the Object Properties dialog. Object Properties: BarGraph Use the Object Properties dialog to specify the following parameters: • Tag/Expression field: Type a tag or expression that evaluates the bar graph level. You also can click the icon to browse your directories for an existing tag or expression. • Minimum Value field:
Type a numeric constant or a tag value into this field to define the minimum value used to calculate the height (if vertical) or width (if horizontal) of the bars. • Maximum Value field: Type a numeric constant or a tag value into this field to define the maximum value used to calculate the height (if vertical) or width (if horizontal) of the bars. If you do not specify a value for this field, the application opens a dialog requesting you confirm creation of the tag. Tip: The application also allows you to enter constants in tag/numeric value fields. Constant values (defined by the # character) are equivalent to numeric values, except that constants display in the Tag Replace dialog.
You may find constants useful for documentation purposes or for creating generic objects. For example: #Name:100 . Where the value ( 100 ) following the semicolon ( : ) is the constant, and Name is a constant mnemonic only and not added to database. • Foreground Color : To specify a fill color for the bars, click the combo-box button. When the Color dialog displays, click on a color to select it, and then close the dialog. • Direction area: Click the Vertical or Horizontal radio button to specify the direction of the bar graph. • Orientation area: Click the Up , Center , or Down radio button to specify the orientation of the maximum and minimum values when drawing the bars.
TEXT DATA LINK ANIMATION On the Graphics tab, in the Animations group, click Text Data Link to add the animation input or output text property to a selected Text object. Applying the Text Data Link property allows you to insert and display tag values in real time if you are using the keyboard or on-screen keypad to run a project. Note: You can only apply this animation to Text objects that include one or more # characters. Each # represents one character of input/output. You can combine # characters with regular text in the same Text object — for example, MyLabel ##### or $###.## . Page 204 InduSoft Web Studio