Communication with Other Devices You can right-click on a driver subfolder to access the Settings option, which opens the Communications Parameters dialog. Sample Communications Parameters dialog Use the parameters on this dialog, as follows: • Serial Encapsulation field: Enables serial drivers to communicate with modem, TCP/IP or UDP connections. This setting is supported only for serial drivers developed with the UNICOMM library, which includes most of the serial drivers available in the product. Caution: The Modem option is not supported for Pocket PC v3.00 or older. Note: This section covers only the None option, which enables the driver to connect using a normal serial channel.
Please refer to "Using TCP/IP and UDP Encapsulation" and "Using Modem Connections" below for more information about other encapsulation modes. "Serial Encapsulation Tests" below lists the drivers that have been tested with modem, TCP/IP and UDP modes. • COM field: Click to select a serial communication port. • Baud Rate , Data Bits , Stop Bits , and Parity fields: Click to select parameters for a serial port configuration. • Long1 , Long2 , String1 , and String2 fields: These fields are driver custom settings. In the example above, the driver uses Long1 to set up the error detection method and String1 to define the PLC family type. • Advanced button:
Click to open the Advanced settings dialog. Use this dialog to change the default driver parameters. Advanced Settings dialog Specify or change the default driver parameters as follows: • Timeout (ms) area: • Start message field: Specify the timeout for the message start. • End message field: Specify the timeout for the message end. • Interval between char field: Specify the timeout between each character. • Wait CTS field: Specify the timeout for the Clear to Send wait. • Handshake area: • Control RTS drop-down list: Specify whether to use the "Request to Send" control. Page 292 InduSoft Web Studio