omron — OPC UA

Communication with Other Devices A new OPC UA Client worksheet is displayed: OPC UA Client worksheet 2. In the Description box, type a description of the worksheet. This is for documentation purposes only and does not affect the execution of the worksheet. 3. In the Connection list, select the OPC Server connection that you configured earlier. 4. For more connection options, click Advanced . The Advanced dialog is displayed: Review the options and configure as needed: InduSoft Web Studio Page 305 Area / Element Description Read actions Enable subscription When this value is TRUE (non-zero), the client will constantly request updates from the server. Note: This is enabled by default.

If it is disabled, then you must use read triggers (see below). Maximum group size The maximum number of tag reads that may be performed in a single read operation. For example, if you have 1000 items/rows configured in the worksheet and Maximum group size is set to 100, then 10 read operations will be performed during each scan of the worksheet. Synchronous read trigger When the value of this tag/expression changes, the worksheet is scanned and all tag values are read from the server. The project waits for the scan to complete before continuing. Asynchronous read trigger When the value of this tag/expression changes, the worksheet is scanned and all tag values are read from the server.

The project continues running without waiting for the scan to complete. Read count The name of a tag (Integer type) that will receive a count of the number of read operations performed since the project was run.