Delta ISPSoft — B.1.1 AH/AS Series Device Types

Appendix B Notification for PLC Types *1. AH/AS series CPU modules support the manipulation of the bits in the input relays, the output manipulated, Y0.1 indicates that bit 1 in Y0 is manipulates, D0.1 indicates that bit 1 in D0 is relays, the data registers, and the link registers. For example, X0.1 indicates that bit 1 in X0 is manipulates, and L0.1 indicates that bit 1 in L0 is manipulated. Please refer to the following sections for more information. *2. A link register is used for data exchange, but it can also be used as a general data register. There is no link register for AS series PLC. *3. The index registers that AH/AS series CPU modules have are E devices.

AH500 series CPU modules do not have F devices. *4. AH/AS series PLCs are different from DVP series PLCs in that the special auxiliary relays and the special data registers in AH500 series PLCs are called SM devices and SR devices. Please refer to Programming Manual or PLC Instructions and Special Registers Reference in a project for a CPU module in ISPSoft for more information. B-3 Device Access Description type property Word 32-bit counter: If a 32-bit counter is used as a word device, the value stored in the 32-bit counter is the present value of the 32-bit counter. E Word Index register: The value stored in an index register indicates the offset for a device modified.

(*3) SM Bit Special auxiliary relay: It is used as a state flag for a special function of the system. (*4) SR Word Special data register: It is used as a data register for a special function of the system. (*4)