Delta ISPSoft — 3.1.4.13 Ethernet Port Advance Setting – RTU Mapping

ISPSoft User Manual  Users can select RTU1 Enable to enable this RTU function. Each RTU can be set individually.  Users can set a station address and IP address.  Users can set RX mapping address and RX mapping length to make the digital input points of DI module connected to RTU mapped to X/M devices and length of PLC CPU. While, the RY mapping address and length set is used for making the digital output points of DO module mapped to Y/M devices and length of PLC CPU.  Users can set RCR Read mapping address and RCR Read mapping length to make the analog input points of AI module connected to RTU mapped to D/SR devices and length of PLC CPU.

While, the RCR Write mapping address and length set is used for making the analog output points of AO module mapped to D/SR devices and length of PLC CPU. 3-104