ISPSoft User Manual 3.1.4.15 Function Card 2 Setting The Function Card 2 Setting table is used for setting parameters of function card 2 in AS300 series CPU module, which is installed by inserting to the slot. Besides function card 2 settings, the option also include settings for AS-FEN02 and IP filter. For function card 2, AS-FCOPM and AS-FEN02 in Manual Select Card box are additional options that does not exist for function card 1. If users select AS-FCOPM card, the parameters can be set in the following window. Users can select AS Remote Control/Delta Servo Drives and AS Remote Module/CANopen DS301 from the AS-FCOPM working mode box.
The AS Remote Module and Delta Servo Drives adopts communication protocols exclusive to Delta servo products and AC motor drives. In addition, the AS Remote Module and Delta Servo Drives are also applied in connecting remote I/O AS series as well as CANopen DS301 for the application of DS301 standard protocol. Users can set the address of the station when CANopen DS301 is selected from the AS-FCOPM working mode box. The remote I/O parameters can be set if AS Remote Mode is selected from the AS-FCOPM working mode expansion module. box. The AS Remote Module No.
sets the number of remote I/O modules and each one can connect an If AS Remote Mode/Delta servo drives and AS Remote Mode is selected from the AS-FCOPM working mode box, users can Select run mode after detect remote module to run the number of actual connected modules inconsistent with the set number of modules, then the actual connected remote module operating or all remote modules will stop running; AS CPU keep or Stop when slave node dis-connected only shows errors or stops running and sends an alarm when the remote I/O module is disconnected during operation ; AS Remote and CANopen Communication Timeout sets the timeout during which the remote I/O module does not give a reply ; Auto Retry connection after Disconnected 3-106