6.6 Operator Programming Errors 6.6 Operator Programming Errors An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting is inappropriate. The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE occurs, investigate the cause and Refer to oPE Codes, Causes, and Possible Solutions on page 132 for the appropriate action.
u oPE Codes, Causes, and Possible Solutions Table 6.9 oPE Codes, Causes, and Possible Solutions 132 SIEP C710606 33A OYMC AC Drive – J1000 User Manual LED Operator Display Error Name oPE01 Drive Capacity Setting Fault Drive capacity and then value set to o2-04 do not match. Cause Possible Solutions The drive capacity setting (o2-04) and the actual capacity of the drive are not the same. Correct the value set to o2-04. LED Operator Display Error Name oPE02 Parameter Range Setting Error Cause Possible Solutions Parameters were set outside the possible setting range. Set parameters to the proper values. Note:
Other errors are given precedence over oPE02 when multiple errors occur at the same time. LED Operator Display Error Name oPE03 Multi-Function Input Selection Error A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-05. Cause Possible Solutions • The same function is assigned to two multi-function inputs. • Excludes “Not used” and “External Fault.” • Ensure all multi-function inputs are assigned to different functions. • Re-enter the multi-function settings to ensure this does not occur. The Up command was set but the Down command was not, or vice versa (settings 10 vs. 11). Correctly set functions that need to be enabled in combination with other functions.
Run command for a 2-Wire sequence was set, but forward/reverse command for a 2-Wire sequence was not. Correctly set functions that need to be enabled in combination with other functions. The following two functions are set at the same time: • Up/Down Command (10 vs. 11) • Hold Accel/Decel Stop (A) • Check if contradictory settings have been assigned to the multi-function input terminals at the same time. • Correct setting errors. One of the following settings is set at the multi-function input terminals: • External Search Command 1 and External Search Command 2 (61 vs. 62) • Fast-Stop N.O. and Fast-Stop N.C. (15 vs.
17) LED Operator Display Error Name oPE05 Run Command/Frequency Reference Source Selection Error Cause Possible Solutions Frequency reference is assigned to an option unit (b1-01 = 2 or 3) that is not connected to the drive. Reconnect the option unit to the drive. The Run command is assigned to serial communication (b1-02 = 2) but no communication option is connected to the drive. LED Operator Display Error Name oPE10 V/f Data Setting Error The following setting errors have occurred where: E1-04 is greater than or equal to E1-06 is greater than or equal to E1-07 is greater than or equal to E1-09. Cause Possible Solutions — Correct the settings for E1-04, -06, -07 and -09.
LED Operator Display Error Name oPE11 Carrier Frequency Setting Error Correct the setting for the carrier frequency. Cause Possible Solutions The following simultaneous contradictory settings: C6-05 is greater than 6 and C6-04 is greater than C6-03 (carrier frequency lower limit is greater than the upper limit). If C6-05 is less than or equal to 6, the drive operates at C6-03. Correct the parameter settings. Upper and lower limits between C6-02 and C6-05 contradict each other.