omron — E: Motor Parameters

B.2 Parameter Table Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency Reference Upper Limit. Parameter can be changed during run. u E: Motor Parameters E parameters set V/f characteristics and motor-related data. Values shown here are for 200 V class drives. Double the value when using a 400 V class drive. Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller. Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection. 174 SIEP C710606 33A OYMC AC Drive – J1000 User Manual No. Name Description Range Def. Mode Addr. Hex Pg.

d3-01 Jump Frequency 1 d3-01 to d3-04 allow programming of three prohibited frequency reference points for eliminating problems with resonant vibration of the motor/machine. This feature does not eliminate the selected frequency values, but accelerates and decelerates the motor through the prohibited bandwidth. The parameters must be according to the rule d3-01 ≥ d3-02 . 0.0 to 400.0 0.0 Hz O 294 84 d3-02 Jump Frequency 2 0.0 Hz O 295 84 d3-04 Jump Frequency Width This parameter sets the dead-band width around each selected prohibited frequency reference point. The bandwidth becomes the designated Jump frequency, plus or minus d3-04. 0.0 to 20.0 1.0 Hz O 297 84 d4:

Frequency Reference Hold Use d4 parameters to configure the drive frequency reference hold function. d4-01 Frequency Reference Hold Function Selection Determines if the frequency reference or frequency reference bias is saved when the Run command is removed or the power goes off. 0: Disabled 1: Enabled This parameter is effective when the multi-function inputs “Accel/ Decel Ramp Hold” or “Up/Down” commands are selected (H1-  = A or 10/11). 0, 1 0 O 298 84 No. Name Description Range Def. Mode Addr. Hex Pg. E1: V/f Pattern Characteristics Use E1 parameters to set V/f characteristics for the motor. E1-01 Input Voltage Setting This parameter must be set to the power supply voltage. WARNING!

Drive input voltage (not motor voltage) must be set in E1-01 for the protective features of the drive to function properly. failure to do so may result in equipment damage and/or death or personal injury. 155 to 255 200 S 300 86 E1-04 Max Output Frequency To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these rules:

E1-04 ≥ E1-06> E1-07 ≥ E1-09 VACrms Out (V) E1-05 E1-08 E1-10 E1-09 E1-07 E1-06 E1-04 Frequency (Hz) 40.0 to 400.0 50 Hz S 303 86 E1-05 Max Output Voltage 0.0 to 255.0 200 V S 304 86 E1-06 Base Frequency 0.0 to E1-04 50 Hz O 305 86 E1-07 Mid Output Frequency 0.0 to E1-04 2.5 Hz O 306 86 E1-08 Mid Output Frequency Voltage 0.0 to 255.0 16.0 V O 307 86 E1-09 Minimum Output Freq. 0.0 to E1-04 1.3 Hz S 308 86 E1-10 Minimum Output Freq. Voltage 0.0 to 255.0 12.0 V O 309 86 E2: Motor Parameters Use E2 parameters to set motor-related data. E2-01 Motor Rated Current Sets the motor nameplate full load current in amperes (A).

10 to 200% of drive rated current S 30E 88 E2-02 Motor Rated Slip Sets the motor rated slip in Hertz. 0.00 to 20.00 O 30F 88 E2-03 Motor No-Load Current Sets the magnetizing current of the motor in Ampere. 0 to less than E2-01 O 310 88 E2-05 Motor Line-to-Line Resistance Sets the phase-to-phase motor resistance in ohms. 0.000 to 65.000 O 312 88