omron — d1: Frequency Reference

5.4 d: Reference Settings 5.4 d: Reference Settings The drive offers various ways of entering the frequency reference. The figure below gives an overview of the reference input, selections, and priorities. b1-01 (Freq. Reference Source 1) 0 ComRef Digital Input H1-  = 2 REMOTE MS 1 LOCAL d1-02 MS 2 d1-03 MS 3 0 Frequency Reference Frequency Reference 2 through 8 d1-04 MS 4 1 d1-07 d1-08 MS 7 MS 8 Jog Frequency d1-17 Jog Multi-Step Speed Digital Input (H1-  ) Jog Reference (=6) Figure 5.8 Frequency Reference Setting Hierarchy u d1: Frequency Reference n d1-01 to d1-08, d1-17:

Frequency Reference 1 to 8 and Jog Reference Up to 9 preset references (including Jog reference) can be programmed in the drive. The references can be switched during Run by digital inputs. The acceleration/deceleration to the new reference is performed using the active acceleration/ deceleration time. The Jog frequency must be selected by a separate digital input and has priority over the references 1 to 8. Multi-speed reference 1 can be provided by analog input A1. The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).

Multi-Step Speed Selection Depending on how many speeds are used, some digital inputs have to be programmed for Multi-Step Speed Selection 1, 2, 3 and 4 (H1-  = 3, 4, 5). For the Jog reference a digital input must be set to H1-  = 6. Notes on using analog inputs as multi-speed 1 and 2: • If the frequency reference source is assigned to analog input A1 (b1-01 = 1), then this input will be used for Frequency Reference 1 instead of d1-01. If the reference source is assigned to the digital operator (b1-01 = 0), then d1-01 will be used as Frequency Reference 1. The different speed references can be selected as shown in Table 5.9 . Figure 5.9 illustrates the multi-step speed selection.

Table 5.9 Multi-Step Speed Reference and Terminal Switch Combinations 82 SIEP C710606 33A OYMC AC Drive – J1000 User Manual Option Card =3 =2 =1 =0 MEMOBUS comm. TerminalA1 d1-01 (Freq.Ref 1) 1 No.

Parameter Name Setting Range Default d1-01 to d1-08 Frequency Reference 1 to 8 0.00 to 400.00 Hz 0.00 Hz d1-17 Jog Frequency Reference 0.00 to 400.00 Hz 6.00 Hz Reference Multi-Step Speed H1- = 3 Multi-Step Speed 2 H1- = 4 Multi-Step Speed 3 H1- = 5 Jog Reference H1- = 6 Frequency Reference 1 (d1-01/A1) OFF OFF OFF OFF Frequency Reference 2 (d1-02) ON OFF OFF OFF Frequency Reference 3 (d1-03) OFF ON OFF OFF Frequency Reference 4 (d1-04) ON ON OFF OFF Frequency Reference 5 (d1-05) OFF OFF ON OFF Frequency Reference 6 (d1-06) ON OFF ON OFF Frequency Reference 7 (d1-07) OFF ON ON OFF