Victron Energy B.V. · MultiPlus-II Series Inverters · 1 pp.

Victron MultiPlus-II Inverter User Manual & Service Guide PDF

Паспорт продукта для инверторов MultiPlus-II, подтверждающий соответствие стандартам NRS 097-2-1 для систем параллельной подключения через инвертор к сетям общественного электроснабжения.

Related manuals

Document text

Certificate No. 26-001-00 Certificate Applicant: Victron Energy B.V. De Paal 35 1351 JG Almere Netherlands Product: Battery inverter with integrated automatic disconnection device between a generator and the public low-voltage grid Model: MultiPlus-II 48/3000/35-32 230V, MultiPlus-II 48/3000/35-32 230V GX, MultiPlus-II 48/5000/70-50 230V, MultiPlus-II 48/5000/70-50 230V GX, MultiPlus-II 24/3000/70-32 230V, MultiPlus-II 24/3000/70-32 230V GX, MultiPlus-II 48/4k5/55-32 230V, MultiPlus-II 48/4k5/55-32 230V GX, MultiPlus-II 48/6k5/100-50 230V, MultiPlus-II 48/6k5/100-50 230V GX Intended use:

Automatic disconnection device with single-phase mains surveillance in accordance with NRS 097-2-1 for systems with a single-phase parallel coupling via an inverter in the public mains supply. The automatic disconnection device is an integral part of the aforementioned inverter. Applied standards and guidelines: SOP-9-1_15 GCC Certification Program, 09/21 Based on: NRS 097-2-1:2024, Edition 3 Grid interconnection of embedded generation Part 2: Small-scale embedded generation Section 4:

Utility compatibility The safety concept of an aforementioned representative product corresponds at the time of issue of this certificate to the valid safety specifications for the specified use in accordance with regulations. Limitation: If the inverter detects voltages of 115%Un the inverter immediately switches to a “VRT/UPS” mode. This mode consists in the inverter stops injecting current into the grid (at the AC-IN port) but continues to inject current to the loads connected to the AC-OUT ports 1 and/or 2. Kiwa Primara GmbH GewerbestraЯe 28 - 32 87600 Kaufbeuren Germany Tel. +49 8341 99726-0 primara@kiwa.com www.kiwa.de Report No: 17PP264-49_0 Date of issue:

2026-01-14 Tanja Rottach - Digitally signed | see http://ca.kiwa-deutschland.de for more details - TC_ NRS097-2-1_B Tanja Rottach Certification Engineer