mean-well KNX Application Database - DLC-02-KN-E — 页 199

4.1.2.2 DALI setting-Standby switch-off 4.1.2.1 DALI setting-KNX failure Behavior after KNX Bus power up Value Behavior after KNX Bus power down Value defined value v 100% - defined value : 0%(OFF) v lf the current object “Standbyy switch-off" is "OFF", the’Behavior after KNX Bus power down” will not have enough time to act. The chart shows the dynamic range for this parameter: ETS-text Behavior after KNX Bus power up Dynamic range [default value] @ switch-off value Uses this parameter to set the behaviors of the connected @ switch-on value ECGs/lamps in DALI Bus A and B when KNX bus is on/ return.

@ no action Actions are all off, all on, no @ defined value action, all set to a certain value @ last value Value or all stay at last value. @ 0~100% [100%] @ broadcast off Behavior after KNX @ broadcast on Bus power down @ no action @ defined value Value Comment @ 100% 9 © 99% “ @ 0.8% @ 0.4% @ 0%(OFF) 15 This option is only available when "Behavior after KNX Bus power up" is selected as “defined value". Use this parameter to set a desired value Uses this parameter to set the behaviors of the connected ECGs/lamps in DALI Bus A and B when KNX bus voltage The "Standby switch-off" function can save energy by switching off the AC power of all DALI drivers that are in standby on the Bus Aor B.

This function is used in conjunction with the KNX switch actuator (KAA-8R) to automatically turn on or off the AC power of the DALI drivers. All DALI drivers are connected to AC, and when the KNX bus is powered on, object 19 and object 42 "Standby switch-off" report "1". Determines whether all DALI drivers on bus A or B are in standby by polling. When all DALI drivers on bus A or B are in standby, the "Standby switch-off" function is triggered to turn off the AC of all DALI drivers on that bus. After polling once, it will automatically determine whether the "Standby switch-off" condition is satisfied according to the state of the KNX object "ECG on/off".

In addition, ECG adds the parameter "Be in control of standby switch off" to determine whether this DALI driver is amember of the standby shutdown function condition. For example, ECG 1 and ECG 2 enable "Be in control of standby switch off", while ECG 3 disables this parameter. If ECG 1 and ECG 2 are OFF, whether ECG 3 is ON or OFF, the object "Standby switch off" will send "0" to turn off the AC of ECG 1 and ECG 2. Note: 1.

During DCA debugging, the "Standby switch off" function is automatically disabled by default; 2.When using the "Standby switch off” function, please set the parameter "Behavior after KNX Bus power down" of the relay associated with the object "Standby switch off" to "ON". falls down. Actions are all off, all on, no action or all set to a certain value h | abi This option is only available when “Behavior after KNX Bus power down" is selected as "defined value”. Use this parameter to set a desired value 16