ETS-text Dynamic range [default value] Prolong time @ 0-20min on recovery* [0] test interval* Activate Rest Mode" Sets the time to remain in the extended emergency mode after main voltage recovery Set the time interval for automatic function testing. Note: The functional testing interval is defined in days Function object” Comment (1 to 255). After the end of @ 0-255days [2] each interval cycle, a functional test should be initiated. When the DTR value is 0, automatic function testing will be disabled @ no check @ check Set whether the current ECG activates Rest Mode Activate @nocheck | Set whether the current ECG Inhibit @ check object” activates Inhibit Mode Mode” *Note:1.
The above parameters are only reset after downloading the database, and will not be reset when KNX power is restored. 2.Priority:Emergency mode (mains = off) > Function test/ Duration test / Inhibit mode/ Rest mode/ Extended emergency mode > Panic mode > Lock > Normal operation. "Normal operation” includes "Auto off/ Standby switch-off/ Night mode/ Staircase/ Sequence/ Timer/ HCL”. The following chart shows the objects that belong to A:ECGs: Num Object name Length Set the time interval for the converter to perform automatic duration testing. Duration test interval* Note: DURATION TEST INTERVAL is defined in weeks(1 to 97).
After the end of each interval cycle, the duration test should @ 0-97weeks [2] 64 [A:ECG 1] Converter Test 1 byte Control the following coding: Bit 0: Reserved. Bit 1: Start function test Bit 2: Start duration test disabled when the DTR value is 0. Bit 3: Start partial duration test Sets the maximum time after Bit 4: Stop test which the function test or @ 0-255days time* [7] Bit 5: Reset function test done flag duration test must be Bit 6: Reset duration executed. If a test has not test done flag ended within this time the Bit 7 — 255: Reserved result will indicate max delay exceeded. 41 This object is used to start duration test of the converter, function tests and battery status queries.
Furthermore, it allows to stop running test and to reset test flags. These object follows begin, and automatic duration testing will be Test excution Description 42