The following chart shows the objects that belong to DALIA. Num 21 Object name [Dali A] HCL Colour Length 2 bytes Temperature Description Enable this object when'HCL colour temperature source’ is set to 'HCL colour temperature (2-bytes object)’. This object is used to control the colour temperature value of HCL 4.2.4.1.1 HCL colour temperature source - Ramp curve(1-bit object) Color temperature (K) A 4500 If ‘Enable activate HCL object’ is set to ‘check’, then the object is enabled. This object 22 [Dali A] Activate automatic HCL colour function 1 bit activates or disables the automatic HCL colour function. The 3000 2700 value of the telegram:
1=Activate the automatic HCL colour function; 0=Disable the automatic HCL colour function 121 4 5 Tine Ramp curve(1-bit object): 1-bit slope curve group object. It can parameterize the colour temperature slope curve. For example, Object "HCL ramp up/down" (value 0) triggers an ascending gradient, starting at a colour temperature of 3000K, and after4 hours, reaching the set value of 4500K (final colour temperature). Then, the colour temperature value remains at the set value until the "HCL ramp up/down" group object triggers a descent slope (value 1), starting at 4500K and changing to 2700K after 5 hours. Note:
When the "HCL ramp up/down" group object triggers an upward slope, if the current colour temperature of the group/ECG is not the initial colour temperature of the ramp curve, it takes a fixed time of4 seconds to gradually change to the initial colour temperature of the ramp curve before making changes based on the upward slope curve. 122