mean-well KNX Application Database - DLC-02-KN-E — 页 199

(5) About : Display ETS APP version and other information of DLC-02KN (6) Help : Quickly link to the product manual Bus devices Type AO Multi AT DT8-Tc(1500K,500... A2 Multi-RGBW 5.2 DALI Operation interface Through this interface, you can first configure the group and scene of virtual lamps off-line (Other DALI parameters can be configured in the ETS interface, see Chapter 4 for details), and create project files. When installing on site, the actual lamps and virtual lamps can be paired through DALI addressing, and then the pre created project files can be imported into the site for use through the "download" operation. Note:

During the first installation, "Scan" and "Reinstall" make a no difference in searching devices and addressing. After an installation, the "Scan" button carries out a search for previously addressed and unaddressed devices. Address for previously addressed devices will remain unchanged. The next available address is then assigned to devices which have been recently added, whereas "Reinstall" removes all addresses and then re-addresses them randomly. In addition, you can also test lamps, groups, and scenes online, as well as change the DALI short address of lamps.

All parameter configurations (including groups, scenes, etc.) are only displayed in the workspace and will not be immediately loaded into the DALI gateway. To download the configuration to the gateway and ECGs, press the "Partial download" or "Full download” button (2 ) Parameter download DAA : Bens = ean ae oa NO. U0 = G1 Al DT8-Te{1500K,500. 0 ECG 2 A2 Multi-RGBW Scenes DAs lite . Geeuns MOSUL! as 0 0 Oo 0. ECGDescniption SF partisidowniosd §— J Full download =F DAL test ae Addr Type Group NO. Group Description 7 «G3 GE «GS G6 — v Hof 0 GB S ae a re @RReinstall + Full download Partial download : Only download the data of the changed ECG and Groupto the gateway Full download :

Download the data of all ECG and Group to the gateway Note: Please be aware that the download on the DCA interface only programs the DALI configuration data to the gateway and ECGs. The ETS application with parameter settings and group addresses still needs to 5.2.1 DALI Addressing and Parameter Download : ¥ Partial download RwScan ¥ Partial download ~=—_& Full download SF DAU test be downloaded to the device. This is done, as usual, via the normal download process in the ETS. (1 ) DALI Addressing Use the "Reinstall" or "Scan" buttons to start scanning for devices and assign addresses. The scanned devices will be displayed in the far right area :

@Reinstall KosScan During this process, all ECGs are automatically recognized, and each ECG is assigned a short address from 0 to 63, which may take several minutes. As shown in the figure below, there are 3 ECGs (3) DALI test On the DALI test interface, users can quickly test the brightness, colour temperature, and colour effects of online lamps. Before using the DALI test, please scan the online lamps and assign addresses via the "Scan" or "Reinstall" function. t DALI test (short addresses: AO~A2) on the DALIA bus 141 142