Num Object name Length DPT Flag Function [A:ECG 1] 5/7 Dimming Value(Stat percentage 1 byte (DPT5.001) CRT 0 - 100% us) Description Sends the dimming value of the ECG. 1.The parameter "Send dimming value status” chooses "no send, passive stage object". - update value status but no send telegram. 2.The parameter "Send dimming value status " chooses "at change" — send telegram in every dimming value change. 3.The parameter "Send dimming value status" chooses "always at input of telegram” — send telegram in every dimming command. 4.The parameter "Send Status cyclic” is ata certain time value — send telegram at regular intervals. Num/ Object name} Length .
[A:ECG 1] Lbit Auto Off enable 0=Unlock; Lock (DPT1.003) 1=Lock [A:ECG 1] enable O=Lock; 1 bit 58 Lock 1 bit CW (DPT1.003) 1=Unlock cw _n 0=Disable; Description .| This object is used to enable/disable the 1=Enable | Auto Off function of the ECG When ‘Staircase light’ 59 | [A:ECG 1] Stai taircase is selected as ‘active’, 1 bit enable (DPT1.003) CW enable this object. O=Off | value of telegram: 1= . 1=On _ | enable the staircase light light function; 0 = If the parameter ‘Manual switching off" is selected as ‘active’, the Staircase light function can be turned off 60 [A:ECG 1] : Operation Hours 1 bit reset (DPT1.015) CW | resets th + esets the operating 1=Reset | hours counter of the ECG.
Reset [A:ECG 1] time lag(s) 4-Bytes (DPT13.100) CRT | Valuein Second 4 bytes This object is used to lock/unlock the ECG. Priority: Panic mode > Lock > Night mode This object is used to lock/unlock the ECG. Priority: Panic mode > Lock > Night mode enable Flag | Function (DPT1.003) Operation [A:ECG 1] DPT Hours value The operating hours of the ECG in seconds are sent via this object. /When the parameter |"Select data type" is |set to "4 Byte value in second(DTP 13.100)", the unit of operation time value is seconds. 61 The operating hours of the ECG in hours are sent via this object.
[A:ECG 1] Operation Hours 2-Bytes 2bytes) enable (DPT1.003) (CRT | value Valuein Hours When the parameter |"Select data type" is |Set to "2 Byte value in hour (DTP 7.007)", the unit of operation time value is hour. 165 166