beckhoff KS2000 — 4.2.2 Controller: Common settings

Reference Ams block confirmation If a TwinCAT version >= 2.9 gets used, this box needs to be checked for compatibility reasons. Read system clock The cycle tick counter gets copied into the memory range (%MB…) of the BC/BX controller. See Beckhoff Information System: "GetSysTick" Clear outputs on breakpoint Outputs get cleared when the PLC program hits a Breakpoint. PLC terminal bus update ICO: inputs get read prior to the PLC cycle. Outputs get written after the PLC cycle [default]. IOC: inputs get read and outputs get written prior to the PLC cycle. CIO: inputs get read and outputs get written after the PLC cycle.