4. Motion Control Instruction 4.6.33. MOVF_DI Explanation of the instruction: MOVF_DI is used for sending one 32-bit integer to multiple target registers. When EN is on, the content of S1 is sent to the zone with D as the starting register and the data length is specified by S2. When the data length S2 is larger than maximum 64, it is counted as 64. And the part above 64 is invalid. Explanation of input and output parameter of the instruction: Note: When the content of the register is 32-bit data, it will occupy two consecutive registers.
Program example 4-136 DVP-MC operating manual API Move 32-bit integer to multiple registers Controller MOVF DI 160 _ 10MC11T Parameter Data Available Explanation name type device EN “MOVF DI” is executed as “EN” turns on. _ BOOL M,I,Q, constant S1 The source where the data comes from. DINT Constant,D S2 The length of the transmitted zone, the max value for S2 is 64. UINT Constant,D D The starting one of the target registers DINT D