Delta — Appendix A Modbus Communication

Appendix A Data structure of response message: Data structure of abnormality response message: Note: How many bytes of data in request message are determined by the number of bit device where to write the value in the response message.  Set DVP10MC11T M0~M7=1000 0001, M8~M15=0001 1000, M16~M19=0110 via function code 0F; M0 address: 0x0800 Request message: “01 0F 08 00 00 14 03 81 18 06 8B F9” Response message: “01 0F 08 00 00 14 57 A4”  The Indication of Modbus Communication Port LED COM1 LED is RS-232 communication port indicator used by PLC module to show RS-232 communication state.

COM2 LED is RS-485 communication port indicator commonly used by motion control module and PLC module to show RS-485 communication state.

DVP-MC operating manual A-23 Data order Name Byte Byte0 Modbus ID Single byte Byte1 Function code Single byte Byte2 The start address of DVP10MC11T bit device where to write the value High byte Byte3 Low byte Byte4 The number of DVP10MC11T bit devices where to write the value High byte Byte5 Low byte Byte6 Low byte of CRC check sum Low byte Byte7 High byte of CRC check sum High byte Data order Name Byte Byte0 Modbus ID Single byte Byte1 0x80+ function code Single byte Byte2 Abnormality response code High byte Byte3 Low byte of CRC check sum Low byte Byte4 High byte of CRC check sum High byte LED state Indication Yellow light flash There are response data at RS-232(COM1)port.

Off There are no response data at RS-232(COM1)port. RUN state Indication Yellow light flash There are response data at RS-485(COM2)port Off There are no response data at RS-485(COM2)port