Delta — Appendix B Ethernet Communication

Appendix B Response message data structure: Abnormality response message data structure: Note: The written value 0x0000 for bit device in request message or response message indicates be value written in device is 0; the written value 0xFF00 for bit device indicates the value written in device is 1.  Example: Set the value of M0 in DVP10MC11T as 1 via function code 05; the address of M0 is 0x0800. Request message: “ 00 00 00 00 00 06 01 05 08 00 FF 00” Response message:

00 00 00 00 00 06 01 05 08 00 FF 00” DVP-MC operating manual B-11 Data order Name Byte Byte10 The value written in bit device High byte Byte11 Low byte Data order Name Byte Byte0 Transaction identifier High byte Byte1 Low byte Byte2 Protocol identifier High byte Byte3 Low byte Byte4 Modbus data length High byte Byte5 Low byte Byte6 Modbus ID Single byte Byte7 Function code Single byte Byte8 Modbus address of bit device High byte Byte9 Low byte Byte10 The value written in bit device High byte Byte11 Low byte Data order Name Byte Byte0 Transaction identifier High byte Byte1 Low byte Byte2 Protocol identifier High byte Byte3 Low byte Byte4 Modbus data length High byte Byte5 Low byte Byte6 Modbus ID Single byte Byte7 0x80+ function code Single byte Byte8 Abnormality response code Single byte