Victron Energy Lithium NG 51,2V — 5.2.1. Charging the battery and recommended charger settings

Lithium NG 51,2V battery manual 5.1.2. Monitoring the battery via a GX device The battery parameters can also be read out with a GX device via the Remote Console in conjunction with a Lynx Smart BMS NG. The table in the previous section lists the available parameters per connection type. To check the battery parameters, do the following 1. Open the Remote Console, and from the Device List click on the Lynx Smart BMS NG. 2. Scroll down to 'System' and open the submenu by clicking on it to view all available battery parameters. 5.1.3.

Monitoring the battery via the VRM Portal The battery parameters can also be read out via the VRM Portal (requires a GX device in conjunction with a Lynx Smart BMS NG that transmits its data to VRM). The table in the previous section lists the available parameters per connection type. The battery parameters can be viewed via the 'Advanced' tab. For more information, please see our VRM Portal documentation . 5.2. Battery charging and discharging This chapter describes the charging, discharging and cell balancing process in more detail for those who are interested in the technical background. 5.2.1.

Charging the battery and recommended charger settings Recommended battery chargers Ensure your charger supplies the correct current and voltage for the battery, so do not use a 24 V charger for a 12 V battery. It is also recommended that the charger has a charging profile/algorithm that matches the battery chemistry (LiFePO4) or a custom profile that can be adjusted to match the appropriate charging parameters of the lithium battery. All Victron chargers ( AC Chargers including Inverter/Chargers , Solar Chargers and DC-DC Chargers ) have these preset charging profiles built-in. Make sure this profile is selected. See also the respective charger manuals.

Recommended charger settings The important charging parameters are absorption voltage, absorption time and float voltage. Absorption voltage: 14.2 V for a 12.8 V lithium battery (28.4 V / 56.8 V for a 24 V or 48 V system) Absorption time: 2 hours. We recommend a minimum absorption time of 2 hours per month for lightly cycled systems, such as backup or UPS applications, and 4 to 8 hours per month for more heavily cycled (off-grid or ESS) systems. This allows the balancer enough time to balance the cells properly. Float voltage: 13.5 V for a 12.8 V lithium battery (27 V / 54 V for a 24 V or 48 V system) Some charging profiles offer a storage mode.

This is not needed for a lithium battery, but if the charger has a storage mode, then set this to the same value as the float voltage. Page 18 Operation