Victron Energy Lithium NG 51,2V — 6.2.4. The BMS is displaying an alarm while all cell voltages are within range

Lithium NG 51,2V battery manual 6.2. BMS issues 6.2.1. The BMS frequently disables the battery charger A well-balanced battery does not disable the charger, even when it is fully charged. However, when the BMS frequently disables the charger, this indicates cell imbalance. Check the cell voltages of all batteries connected to the BMS using VictronConnect. In case of moderate or large cell imbalance, it is expected behaviour that the BMS frequently disables the battery charger. This is the mechanism behind this behaviour: As soon as one cell reaches 3.75V, the BMS disables the charger.

Whilst the charger is disabled, the cell balancing process still continues, moving energy from the highest cell into adjacent cells. The highest cell voltage will drop; once it has fallen below 3.6V, the charger will be enabled again. This cycling typically takes between one and three minutes. The voltage of the highest cell will rise again quickly (this can be in a matter of seconds), after which the charger will be disabled again, and so forth. This does not indicate a problem with the battery or the cells. This behaviour will continue until all cells are fully charged and balanced. This process might take several hours. It depends on the level of imbalance.

This process can take up to 12 hours in case of serious imbalance. Balancing will continue throughout this process, even when the charger is disabled. The continued enabling and disabling of the charger can appear strange but rest assured that there is no problem. The BMS is merely protecting the cells from overvoltage. 6.2.2. The BMS is prematurely turning chargers off This could be because of a cell imbalance. One cell in the battery has a cell voltage above 3.75V. Check the cell voltages of all batteries connected to the BMS. 6.2.3. The BMS is prematurely turning loads off This could be because of a cell imbalance.

When a cell's voltage falls below the battery's minimum limit of 2.6V, the BMS turns off the load. Check the cell voltages of all batteries connected to the BMS using the VictronConnect app. Once the loads have been turned off due to low cell voltage, the cell voltage of all cells needs to be 3.2V or higher before the BMS will turn the loads back on. 6.2.4. The BMS is displaying an alarm while all cell voltages are within range A possible cause is a loose or damaged BMS cable or connector. First, check that the cell voltages and temperatures of all connected batteries are within range. If they are all in range, then follow one of the following procedures.

Check all BMS cables and their connections. Also consider that once there has been a cell undervoltage alarm, the cell voltage of all cells needs to be increased to 3.2V before the battery clears the undervoltage alarm. A way to rule out if a fault is originating from a faulty BMS or a faulty battery is to check the BMS using one of the following BMS test procedures: Single battery and BMS check: 1. Disconnect both BMS cables from the BMS. 2. Connect a single BMS extension cable between both BMS cable connectors. The BMS cable should be connected in a loop, as shown in the diagram below. The loop tricks the BMS into thinking that a battery is connected without any alarms.