Victron Energy Lithium NG 51,2V — 8.1. Battery specification

Lithium NG 51,2V battery manual 8. Technical data 8.1. Battery specification Page 30 Technical data VOLTAGE AND CAPACITY Battery model LFP 51,2 V/100 Ah Nominal voltage 51,2 V Nominal capacity @ 25 °C* 100 Ah Nominal energy @ 25 °C* 5120 Wh Capacity loss (per 100 cycles, @ 25 °C, 100 % DoD): Energy loss (per 100 cycles, @ 25 °C, 100 % DoD):

Round trip efficiency 92 % * Discharge current ≤ 1C CYCLE LIFE (capacity ≥ 80% of nominal) 80 % DoD 2500 cycles 70 % DoD 3000 cycles 50 % DoD 5000 cycles DISCHARGE Max continuous discharge current (C-rate) 100 A (1C) Max pulse discharge current 10s (C-rate) 200 A (2C) End of discharge voltage 44,8 V Internal resistance 8 mΩ CHARGE Charge voltage Between 56 V and 56,8 V Float voltage 54 V Max continuous charge current (C-rate) 100 A (1C) Max pulse charge current 10s (C-rate) 200 A (2C) GENERAL BMS-es Lynx Smart BMS NG 500 A / 1000 A (M10 busbars), must be purchased separately Cell measurements Cell voltages and temperatures, battery current Battery BMS interface Male + female cable with M8 circular connector with high-speed digital communication, length 50 cm M8 extension cables are available separately for purchase in various lengths between 1 and 5 meters Alarm feature Pre-alarm contact on BMS Bluetooth In the BMS Max batteries per BMS 25 (128 kWh per BMS 3)) Battery firmware updates Battery firmware automatically updated by BMS Repairable Yes (cover can be removed with screws) OPERATING CONDITIONS Operating temperature Discharge:

-20 °C to +50 °C | Charge: +5 °C to +50 °C