Siemens — Siemens SIRIUS 3RW Soft Starters and Solid-State Switching Devices Manual

© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW30, 3RW40 for Standard Applications 3RW30 More information Application examples for normal starting (Class 10) Normal starting Class 10 (up to 20 s with 300 % I n motor ), The soft starter rating can be selected to be as high as the rating of the motor used 1) The mass inertia of the fan is Note: These tables present sample set values and device sizes. They are intended only for the purposes of information and are not binding. The set values depend on the application in question and must be optimized during commissioning.

The soft starter dimensions should be checked where necessary with the Win-Soft Starter software or with the help of Technical Assistance. Status graphs U U N 4 U S Configuration t R on t The 3RW solid-state motor controllers are designed for easy starting conditions. In the event of deviating conditions or in- creased switching frequency, it may be necessary to choose a larger device. For accurate dimensioning, use the Win-Soft Starter selection and simulation program. ON 13/14 If necessary, an overload relay for heavy starting must be se- lected where long starting times are involved. PTC sensors are recommended.

NSB0_01941 t R on t No capacitive elements are permitted in the motor feeder be- tween the SIRIUS 3RW soft starter and the motor (e. g. no reac- tive-power compensation equipment). In addition, neither static systems for reactive-power compensation nor dynamic PFC (Power Factor Correction) must be operated in parallel during starting and ramp-down of the soft starter. This is important to prevent faults arising on the compensation equipment and/or the soft starter. Manual for SIRIUS 3RW30/40 Besides containing all important information on configuring, commissioning and servicing, the manual also contains exam- ple circuits and the technical specifications for all devices.

Win-Soft Starter selection and simulation program With this software, you can simulate and select all Siemens soft starters, taking into account various parameters such as mains properties, motor and load data, and special application re- quirements. All elements of the main circuit (such as fuses, controls and over- load relays) should be dimensioned for direct starting, following the local short-circuit conditions. Fuses, controls and overload relays must be ordered separately. Please observe the maxi- mum switching frequencies specified in the technical specifica- tions.

The software is a valuable tool, which makes complicated, lengthy manual calculations for determining the required soft starters superfluous. Note: When induction motors are switched on, voltage drops occur as a rule on starters of all types (direct starters, wye-delta starters, soft starters). The infeed transformer must always be dimen- sioned such that the voltage dip when starting the motor remains within the permissible tolerance. If the infeed transformer is di- mensioned with only a small margin, it is best for the control volt- age to be supplied from a separate circuit (independently of the main voltage) in order to avoid the potential switching off of the soft starter.

The Win-Soft Starter selection and simulation program can be downloaded from: www.siemens.com/softstarter > Software You can find more information about soft starters on the Internet likewise at: www.siemens.com/softstarter Training course for SIRIUS soft starters (SD-SIRIUSO) Siemens offers a 2-day training course on the SIRIUS solid-state soft starters to keep customers and own personnel up-to-date on configuring, commissioning and maintenance issues. Power electronics schematic circuit diagram Please direct enquiries and applications to: L1 L2 L3 Training Center for Automation and Industrial Solution Gleiwitzer Strasse 555 D-90475 Nьrnberg Telephone: +49 911 895 3202 Telefax:

+49 911 895 3275 E-mail: ingeborg.hoier@siemens.com www.siemens.com/sitrain-cd NSB0_01940 T1 T2 T3 A bypass contact system is already integrated in the 3RW30 soft starter and therefore does not have to be ordered separately. 4/12 Siemens LV 1 · 2010 Application Conveyor belt Roller conveyor Compressor Small fans1) Pump Hydraulic pump Starting parameters • Voltage ramp and current limiting - Starting voltage % - Starting time s 70 60 50 40 40 40 10 10 20 20 10 10