© Siemens AG 2010 SIRIUS 3RW Soft Starters 3RW44 Soft Starters for High-Feature Applications 3RW44 Order No. supplement for connection types With screw terminals With spring-type terminals 4 1) In the selection table, the unit rated current I e refers to the induction motor's rated operational current in the inside-delta circuit. The actual current of the device is approx. 58 % of this value. 2) Soft starter with screw terminals: 3RW44 2. ... 3RW44 4. Delivery time class A 3RW44 5. ... 3RW44 6. Delivery time class B. 3) Control by way of the internal 24 V DC supply and direct control by means of PLC possible. Note: Soft starter selection depends on the rated motor current.

Please observe the notes for the selection of soft starters on Page 4/7. The 3RW44 solid-state soft starters are designed for normal starting (Class 10). (Inertia load of the overall operating mecha- nism J Load Motor ; starting current 350 % x I e for 20 s or similar load). For any other conditions of use, the devices should be selected using the Win-Soft Starter selection and simulation program. For information about rated currents for ambient tem- peratures > 40 °C and switching frequency, see "Technical spec- ifications". 4/39 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof.

Ambient temperature 40 °C Ambient temperature 50 °C DT Very heavy starting (CLASS 30) in inside-delta circuit PU (UNIT, SET, M) PS* PG Weight per PU approx. Rated opera- tional current Ie1) Rated power of induction motors for rated operational voltage Ue Rated opera- tional current Ie Rated power of induction motors for rated operational voltage Ue 230 V 400 V 500 V 690 V 1000 V A kW kW kW kW kW 200 V 230 V 460 V 575 V A hp hp hp hp Order No. Price per PU Inside-delta circuit, rated operational voltage 400 ...

600 V2) 3RW44 23-@BC@5 3RW44 24-@BC@5 3RW44 25-@BC@5 3RW44 25-@BC@5 3RW44 27-@BC@5 1 3 161 -- 90 110 -- -- 196 -- 110 132 -- -- 142 -- -- 100 125 B 173 -- -- 125 150 B 3RW44 35-@BC@5 1 1 unit 131 7.900 1 1 unit 131 7.900 3RW44 36-@BC@5 232 -- 132 160 -- -- 281 -- 160 200 -- -- 352 -- 200 250 -- -- 433 -- 250 315 -- -- 203 -- -- 150 200 B 251 -- -- 200 250 B 312 -- -- 250 300 B 372 -- -- 300 350 B 3RW44 43-@BC@5 1 1 unit 131 11.500 1 1 unit 131 11.500 1 1 unit 131 11.500 1 1 unit 131 11.500 3RW44 43-@BC@5 3RW44 45-@BC@5 3RW44 47-@BC@5 542 -- 315 355 -- -- 617 -- 355 450 -- -- 748 -- 400 500 -- -- 954 -- 560 630 -- -- 1065 -- 630 710 -- -- 485 -- -- 400 500 C 546 -- -- 450 600 C 667 -- -- 600 750 C 856 -- -- 750 950 C 954 -- -- 850 1050 C 3RW44 53-@BC@5 1 1 unit 131 50.000 1 1 unit 131 50.000 1 1 unit 131 50.000 1 1 unit 131 50.000 1 1 unit 131 50.000 3RW44 53-@BC@5 3RW44 53-@BC@5 3RW44 55-@BC@5 3RW44 58-@BC@5 1200 -- 710 800 -- -- 1065 -- -- 950 1200 C 3RW44 65-@BC@5 1 1 unit 131 78.000 1351 -- 800 900 -- -- 1200 -- -- 1050 1350 C 3RW44 65-@BC@5 1 1 unit 131 78.000 1524 -- 900 1000 -- -- 1351 -- -- 1200 1500 C 3RW44 65-@BC@5 1 1 unit 131 78.000 -- -- -- -- -- -- 1472 -- -- 1300 1650 C 3RW44 66-@BC@5 1 1 unit 131 78.000 Order No.

supplement for connection types • With spring-type terminals 2 • With screw terminals 6 Order No. supplement for the rated control supply voltage Us3) • 115 V AC 3 • 230 V AC 4 3RW44 65-@BC@5 3RW44 65-@BC@5 3RW44 65-@BC@5 3RW44 66-@BC@5