© Siemens AG 2010 Solid-State Switching Devices for Resistive Loads Solid-State Contactors General data Overview Solid-State Contactors The complete units consist of a solid-state relay plus optimized heat sink, and are therefore ready to use. They offer defined rated currents to make selection as easy as possible. Depend- ing on the version, current strengths of up to 88 A are achieved. Like all of our solid-state switching devices, one of their particu- lar advantages is their compact and space-saving design. With their insulated mounting foot they can easily be snapped onto a standard mounting rail, or they can be mounted on sup- port plates with fixing screws.

This insulation enables them to be used in circuits with protective extra-low voltage (PELV) or safety extra-low voltage (SELV) in building management systems. For other applications, such as for extended personal safety, the heat sink can be grounded through a screw terminal. The solid-state contactors are available in 2 different versions: • 3RF23 single-phase solid-state contactors, • 3RF24 three-phase solid-state contactors 1) The miniature circuit breakers can be used up to a maximum rated voltage of 480 V!

4 Single-phase versions 3/N/PE 50 Hz 230/400 V 3/N/PE 50 Hz 230/400 V The 3RF23 solid-state contactors can be expanded with various function modules to adapt them to individual applications. L2 L1 L2 L1 Version for resistive loads, "zero-point switching" L3 N L3 N This standard version is often used for switching space heaters on and off. F1 F1 F2 Version for inductive loads, "instantaneous switching" K1 K1 In this version the solid-state contactor is specifically matched to inductive loads.

Whether it is a matter of frequent actuation of the valves in a filling plant or starting and stopping small operating mechanisms in packet distribution systems, operation is carried out safely and noiselessly. Special "Low noise" version I,A line line I,A line Thanks to a special control circuit, this special version can be used in public networks up to 16 A without any additional mea- sures, such as interference suppressor filters. As a result, in terms of emitted interference, it conforms to limit value curve class B according to EN 60947-4-3.

NSB0_01473b Special "Short-circuit proof" version The setup and installation above can also be used for the solid- state relays with a I 2 t value of at least 6600 A 2 s. R1 R1 Skillful matching of the power semiconductor with the perfor- mance capacity of the solid-state contactor means that "short- circuit strength" can be achieved with a standard miniature cir- cuit breaker. In combination with a B-type MCB or a conventional line protection fuse, the result is a short-circuit proof feeder.

Three-phase versions The three-phase solid-state contactors for resistive loads up to 50 A are available with • two-phase control (suitable in particular for circuits without connection to the neutral conductor) and • three-phase control (suitable for star circuits with connection to the neutral conductor or for applications in which the system requires all phases to be switched). In order to achieve problem-free short-circuit protection by means of miniature circuit breakers, however, certain boundary conditions must be observed.

As the magnitude and duration of the short-circuit current are determined not only by the short-cir- cuit breaking response of the miniature circuit breaker but also the properties of the wiring system, such as the internal resis- tance of the input to the network and damping by controls and cables, particular attention must also be paid to these parame- ters. The necessary cable lengths are therefore shown for the main factor, the line resistance, in the table below. The converter function module can be snapped onto both ver- sions for the simple power control of AC loads by means of ana- log signals.

• Check the correct contactor size with the aid of the rated cur- rent diagram, taking account of the installation conditions The following miniature circuit breakers with a B characteristic and 10 kA or 6 kA breaking capacity protect the 3RF23..-.DA.. solid-state contactors in the event of short-circuits on the load and the specified conductor cross-sections and lengths: 4/54 Siemens LV 1 · 2010 Rated current of the miniature circuit breaker Example of type1) Max.

conductor cross-section Minimum cable length from contactor to load 6 A 5SY4 106-6, 5SX2 106-6 1 mm2 5 m 10 A 5SY4 110-6, 5SX2 110-6 1.5 mm2 8 m 16 A 5SY4 116-6, 5SX2 116-6 1.5 mm2 12 m 16 A 5SY4 116-6, 5SX2 116-6 2.5 mm2 20 m 20 A 5SY4 120-6, 5SX2 120-6 2.5 mm2 20 m 25 A 5SY4 125-6, 5SX2 125-6 2.5 mm2 26 m 1 2 L T 1 2 L T