© Siemens AG 2010 SIRIUS 3RW Soft Starters General data Overview 4 1) Only soft starting available for 3RW30. 2) Optional up to size S3 (device variant). 3) Available for 3RW40 2. to 3RW40 4.; optional for 3RW40 5. and 3RW40 7.. 4) Calculate soft starter and motor with size allowance where required. 5) Not possible in inside-delta circuit. 6) Trace function with Soft Starter ES software. 7) Use upstream disconnect mechanism You can find further information on the Internet at: www.siemens.com/softstarter 4/6 Siemens LV 1 · 2010 SIRIUS 3RW30 SIRIUS 3RW40 SIRIUS 3RW44 Standard applications Standard applications High-feature applications Rated current at 40 °C A 3 ... 106 12.5 ... 432 29 ...
1214 Rated operational voltage V 200 ... 480 200 ... 600 200 ... 690 Motor rating at 400 V • Inline circuit kW 1.5 ... 55 5.5 ... 250 15 ... 710 • Inside-delta circuit kW -- -- 22 ... 1200 Ambient temperature °C -25 ... +60 -25 ... +60 0 ... +60 Soft starting/ramp-down ✔1) ✔ ✔ Voltage ramp ✔ ✔ ✔ Starting/stopping voltage % 40 ... 100 40 ... 100 20 ... 100 Starting and ramp-down time s 0 ... 20 0 ... 20 1 ... 360 Torque control -- -- ✔ Starting/stopping torque % -- -- 20 ... 100 Torque limit % -- -- 20 ... 200 Ramp time s -- -- 1 ...
360 Integral bypass contact system ✔ ✔ ✔ Intrinsic device protection -- ✔ ✔ Motor overload protection -- ✔ ✔ Thermistor motor protection -- ✔2) ✔ Integrated remote RESET -- ✔3) ✔ Adjustable current limiting -- ✔ ✔ Inside-delta circuit -- -- ✔ Breakaway pulse -- -- ✔ Creep speed in both directions of rotation -- -- ✔ Pump ramp-down -- -- ✔4) DC braking -- -- ✔4) 5) Combined braking -- -- ✔4) 5) Motor heating -- -- ✔ Communication -- -- With PROFIBUS DP (optional) External display and operator module -- -- (optional) Operating measured value display -- -- ✔ Error logbook -- -- ✔ Event list -- -- ✔ Slave pointer function -- -- ✔ Trace function -- -- ✔6) Programmable control inputs and outputs -- -- ✔ Number of parameter sets 1 1 3 Parameterization software (Soft Starter ES) -- -- ✔ Power semiconductors (thyristors) 2 controlled phases 2 controlled phases 3 controlled phases Screw terminals ✔ ✔ ✔ Spring-type terminals ✔ ✔ ✔ UL/CSA ✔ ✔ ✔ CE marking ✔ ✔ ✔ ATEX explosion protection -- ✔7) -- Soft starting under heavy starting conditions -- -- ✔4) Configuring support Win-Soft Starter, electronic selection slider ruler, Technical Assistance +49 911 895 5900 ✔ Function is available; -- Function is not available.