Siemens — Siemens SIRIUS 3RW Soft Starters and Solid-State Switching Devices Manual

© Siemens AG 2010 Solid-State Switching Devices for Switching Motors Solid-State Contactors General data More information Connection methods Short-circuit protection You can choose between the following connection methods for the solid-state contactors for switching motors: Despite the rugged power semiconductors that are used, solid- state switching devices respond more sensitively to short-cir- cuits in the load feeder. Consequently, special precautions have to be taken against destruction, depending on the type of de- sign. Screw connection The screw connection system is the standard among industrial controls. Open terminals and a plus-minus screw are just two features of this technology.

Two conductors of up to 6 mmІ can be connected in just one terminal. As a result, loads of up to 50 A can be connected. Siemens generally recommends using SITOR semiconductor fuses. These fuses also provide protection against destruction in the event of a short-circuit even when the solid-state contactors and solid-state relays are fully utilized. Spring-type terminal connection system Alternatively, if there is lower loading, protection can also be pro- vided by standard fuses or miniature circuit breakers. This pro- tection is achieved by overdimensioning the solid-state switch- ing devices accordingly. This innovative technology manages without any screw connec- tion.

This means that very high vibration resistance is achieved. Two conductors of up to 2.5 mmІ can be connected to each ter- minal. As a result, loads of up to 20 A can be dealt with. 4 Specification 1) These products were built as Class A devices. The use of these devices in residential areas could result in lead in radio interference. In this case these may be required to introduce additional interference suppression measures. 4/74 Siemens LV 1 · 2010 Order No. 3RF24 ..-.BB.., 3RF24 ..-.BD.. General data Ambient temperature • During operation, derating from 40 °C °C • During storage °C -25 ... +60 -55 ... +80 Installation altitude m 0 ...

1000; derating over 1000 m upon request Shock resistance acc. to IEC 60068-2-27 g/ms 15/11 Vibration resistance acc. to IEC 60068-2-6 g 2 Degree of protection IP20 Insulation strength at 50/60 Hz V rms (main/control circuit to floor) 4000 Electromagnetic compatibility (EMC) • Emitted interference acc. to IEC 60947-4-3 - Conducted interference voltage - Emitted, high-frequency interference volt- age • Interference immunity - Electrostatic discharge kV acc. to IEC 61000-4-2 (corresponds to degree of severity 3) - Induced RF fields MHz acc. to IEC 61000-4-6 - Burst acc. to IEC 61000-4-4 kV - Surge acc.

to IEC 61000-4-5 kV Class A for industrial applications1) Class A for industrial applications Contact discharge: 4; Air discharge: 8; Behavior criterion 2 0.15 ... 80; 140 dBμV; Behavior criterion 1 2/5 kHz; behavior criterion 1 Conductor - Ground: 2; Conductor - Conductor: 1; Behavior criterion 2 Permissible mounting positions ±10° ±10° NSB0_01703