© Siemens AG 2010 BETA Measuring Three-Phase Measuring Devices 7KT1 30 multimeters More information Voltage measurement Matrix selection The multimeter measures the delta voltages L1 against L2; L2 against L3 and L3 against L1 or the star voltages L1, L2, L3 against N. Conventional measuring instruments display voltages, currents, powers, etc. in a rigid sequence on several "screens". These multimeters allow users to define their own standard for mea- sured quantities per display field, so that they can be imple- mented far more universally and flexibly. L symbol for the three-phase system This indicates that all physical units shown under this symbol are always 3 phase.

A special feature is the analysis of the different loads on the phases. Phase displacement and unsymmetrical or unbalanced loads can cause partial overloads. These multimeters offer a range of different options for combining and assessing mea- sured values. L1 L1-N The display fields are selected using rotary switches and the de- sired indications confirmed with OK. By making the horizontal selection e. g. W, V, A or p.f., and the vertical selection, e. g. L1, L1 – L2 or L, users can then define the desired measured quantities for this display field. L3-L1 1 L1-L2 l3 l1 2 The vertical data on the display can be assigned to any mea- sured value in the horizontal data.

The letters M(ega) and k(ilo) are automatically assigned according to measuring range, i. e. measured value, e. g. kW or MW. Capacitive loads are automat- ically indicated by a capacitor, inductive loads by a coil. L3-N L2-N 3 N L2 L3 L2-L3 I2_08410b l2 Readout data The following diagram shows an example of what your matrix se- lection might look like. You can continuously display 5 measured quantities from the fol- lowing 23 options. L1 k W L2 L3 OK k W k W A COS L I2_10803a More information about multimeters can be found in Catalog ET B1 · 2010. The current issue of the catalog can be downloaded from www.siemens.com/e-installation-catalogs . 2 set values are also indicated:

24 19 25 19/134 Siemens LV 1 · 2010 No. Measured value Display Unit Assign- ment 1 2 3 4 5 6 Active power D1 W L1 Voltage D1 V L1 Current D1 A L1 Apparent power D1 VA L1 P.f. D1 P.f. L1 Voltage D1 V L1 – L2 7 8 9 10 11 12 Active power D2 W L2 Voltage D2 V L2 Current D2 A L2 Apparent power D2 VA L2 P.f. D2 P.f. L2 Voltage D2 V L2 – L3 13 14 15 16 17 18 Active power D3 W L3 Voltage D3 V L3 Current D3 A L3 Apparent power D3 VA L3 P.f. D3 P.f. L3 Voltage D3 V L3 – L1 19 20 21 22 23 Active power D1, D2, D3, D5 W L Apparent power D1, D2, D3, D5 VA L reactive power D5 var L Frequency D4 Hz L P.f. D1, D2, D3, D4 P.f. L Transformer setting D5 CT/A /5 Transformer setting CT/A 5 ... 5000