© Siemens AG 2010 BETA Protecting Residual Current Protective Devices RCCBs, type A, 5SM3 Overview Benefits RCCBs of type A are used in all systems up to 240/415 V AC. They trip in the event of both sinusoidal AC residual currents and pulsating DC residual currents.

Instantaneous RCCBs with the N-connection on the left-hand side enable simple bus mounting with standard pin busbars with MCBs installed on the right-hand side Instantaneous RCCBs with the N connection on the right-hand side can be bus-mounted with MCBs using a special pin bus- bar Instantaneous devices have a surge current withstand capa- bility with current waveform 8/20 s of more than 1 kA, super resistant of more than 3 kA and selective of more than 5 kA.

This ensures safe operation SIGRES has an extremely long service life due to patented ac- tive condensation protection and the same dimensions for fast and simple exchange of already installed instantaneous RC- CBs Super resistant devices increase plant availability, as unnec- essary tripping is prevented in systems with short-time voltage peaks Selective RCCBs increase plant availability, as in the event of a fault, a staggered tripping time enables the selective trip- ping of RCCBs connected in series Auxiliary switches or remote controlled mechanisms are also available as additional components The operating handle and the test button can be locked by means of a handle locking device.

RCCBs with a rated residual current of maximum 30 mA are used for personnel, material and fire protection, as well as for ad- ditional protection against direct contact. RCCBs with a rated re- sidual current of 10 mA are primarily used in areas that represent an increased risk for personnel. Since the amendment of DIN VDE 0100-410 came into effect in June 2007, all socket outlet current circuits up to 20 A must now also be fitted with residual current protective devices with a rated residual current of max. 30 mA. This also applies to out- door electrical circuits up to 32 A for the connection of portable equipment.

Devices with a rated residual current of maximum 300 mA are used as preventative fire protection in case of insulation faults. RCCBs with a rated residual current of 100 mA are primarily used outside Europe. Note: DIN VDE 0100 is the German version of IEC 60364. SIGRES SIGRES RCCBs were developed for use in harsh ambient con- ditions, such as swimming baths as protection against chlorine and ozone, in the agricultural sector (ammonia), on building sites and in the chemical industry (nitrogen oxide, sulfur dioxide, solvents), in the food processing industry (hydrogen sulfide) and in unheated rooms (dampness).

The patented active condensa- tion protection requires a permanent power supply and the in- feed from below with the RCCBs switched off. Selection criterion For use under ambient conditions according to the product stan- dard (EN 61008-1), the actuation interval for pressing the test button can be extended to once a year. Super resistant ж Equipment Circuit, load current, residual current Super resistant (short-time delayed) RCCBs comply with the maximum permissible break times for instantaneous devices.

However, by implementing a short-time delay they prevent un- necessary trippings, and thus plant faults, when pulse-shaped leakage currents occur - as is the case when capacitors are switched on. System, equipment, ambient conditions Selective о Equipment Can be used as upstream group switch for selective tripping contrary to a downstream, instantaneous or super resistant RCCB. Installation regulation VDE 0100-410 -530 -7xx -482 VDS 3501 Equipment Trip conditions acc.

to VDE 0100-410 Equipment 19 I2_15509a Selection aid for determining a suitable residual current protective device 19/47 Siemens LV 1 · 2010 Design RCCB RCBO RC unit Ty AC A Ver K S SIGR sion ES 500 V 50- 400 Hz Numb 1+N 2 3 er of poles 3+N 4 Rated residua protectio residual cu I∆n Additional Trip c protection lim I ≤ 30 mA ∆n l current I ∆n n objective rrent protection > 30mA onditions Fire ited I protection ∆n I ≤ 300 mA ∆n Rated c urrent I n Only with RCBOs with MCB characteristic B C D