© Siemens AG 2010 BETA Protecting Residual Current Protective Devices SIQUENCE, universal current-sensitive RCCBs type B and type B+, 5SM3 and 5SU1 Overview Benefits Frequency converters, medical devices and UPS systems are seeing increasing use in industry. Smooth DC residual currents or currents with low residual ripple may occur in the event of faults on these devices.
Universal current-sensitive residual current protective devices detect not only AC residual currents and pulsating DC residual currents, but also smooth DC residual currents, thus ensuring the desired protective function with all types of residual cur- rent With type B, the tripping characteristic is adapted to the in- crease of leakage currents at higher frequencies in systems with capacitive impedances and results in increased operat- ing safety. Type B+ versions offer enhanced preventative fire protection and correspond to the prestandards DIN V VDE V 0664-110 and/or DIN V VDE V 0664-210 and VdS Directive 3501. The RCBO is a compact device for up to 125 A.
It provides not only personnel, property and fire protection but also overload and short-circuit protection for cables. This enables great sav- ings on wiring and installation costs. All RCBOs offer external remote tripping over terminals Y1/Y2. This supports implementation of central OFF circuits Type A residual current protective devices are unable to detect these smooth DC residual currents. Furthermore, such smooth DC residual currents make Type A devices increasingly insensi- tive to AC residual currents and pulsating DC residual currents. Hence if a fault occurs, there is no tripping and the desired pro- tection function is no longer assured.
UC-sensitive residual current protective devices of Types B and B+ have an additional transformer which is supplied with a con- trol signal. Hence it is possible to evaluate the change of the transformer's operating range caused by smooth DC residual currents. The desired protection function is thus assured. The residual current protective devices of Type B are suitable for use in three-phase current systems before input circuits with rec- tifiers. They are not intended for use in DC systems and in net- works with operating frequencies other than 50 or 60 Hz.
The devices in this series are designed as residual current oper- ated circuit breakers (RCCBs) up to 80 A and as residual current circuit breakers with integral overcurrent protection (RCBOs) for 100 A or 125 A in Characteristics C or D. Type B+ residual current protective devices additionally offer en- hanced, preventative fire protection. In these versions, the trip- ping value is limited to a maximum of 420 mA up to 20 kHz. Selection and ordering data 19 19/51 Siemens LV 1 · 2010 * You can order this quantity or a multiple thereof. Rated residual Rated current Max. permissi- MW DT current ble short-circuit back-up fuse In In 10 000 mA A A Order No.
Price per PU PU PS* PG Weight per PU approx. Unit(s) Unit(s) kg SIQUENCE RCCBs, type B Super resistant æ 1P+N; 230 V AC; 50 ... 60 Hz 30 16 100 4 A 25 A 40 A 63 A 300 16 100 4 A 25 A 40 A 63 A 3P+N, 230 ... 400 V AC, 50 ...
60 Hz 30 25 100 4 A 40 A 63 A 80 B 300 25 100 4 } 40 A 63 A 80 B 500 63 100 4 B 80 B 1 1 015 0.590 1 1 015 0.590 1 1 015 0.588 1 1 015 0.591 1 1 015 0.600 1 1 015 0.600 1 1 015 0.591 1 1 015 0.586 5SM3 321-4 5SM3 322-4 5SM3 324-4 5SM3 326-4 5SM3 621-4 5SM3 622-4 5SM3 624-4 5SM3 626-4 1 1 015 0.600 1 1 015 0.600 1 1 015 0.600 1 1 015 0.600 1 1 015 0.520 1 1 015 0.520 1 1 015 0.520 1 1 015 0.520 1 1 015 0.520 1 1 015 0.520 5SM3 342-4 5SM3 344-4 5SM3 346-4 5SM3 347-4 5SM3 642-4 5SM3 644-4 5SM3 646-4 5SM3 647-4 5SM3 746-4 5SM3 747-4 SIQUENCE RCCBs, type B Selective î 3P+N, 230 ... 400 V AC, 50 ...
60 Hz 300 63 100 4 B 80 B 500 63 100 4 B 80 B 1 1 015 0.520 1 1 015 0.520 1 1 015 0.520 1 1 015 0.520 5SM3 646-5 5SM3 647-5 5SM3 746-5 5SM3 747-5