Siemens — Siemens BETA Low-Voltage Circuit Protection Manual

© Siemens AG 2010 BETA Protecting Low-Voltage Fuse Systems 3NA, 3ND LV HRC fuse links Overview LV HRC (NH type) fuse systems are used for installation systems in non-residential, commercial and industrial buildings, as well as in the systems of power supply companies. They therefore protect essential building parts and installations. LV HRC fuse links are available in the following operational classes: gG for cable and line protection aM for the short-circuit protection of switching devices in mo- tor circuits gR or aR for the protection of power semiconductors gS: the new gS operational class combines cable and line protection with semiconductor protection.

LV HRC fuse systems are fuse systems designed for operation by skilled personnel. There are no constructional requirements for non-interchangeability of rated current and touch protection. The components and auxiliary equipment are designed in such a way as to ensure the safe replacement of LV HRC fuse systems or isolation of systems. LV HRC fuse links of size 000 can also be used in LV HRC fuse bases, LV HRC fuse switch disconnectors, LV HRC fuse strips as well as in LV HRC in-line fuse switch dis- connectors of size 00. LV HRC fuse links are available in the sizes 000, 00, 0, 1, 2, 3, 4 and 4a. The fuse links 300 A, 355 A and 425 A comply with the standard but do not have the VDE mark.

LV HRC components LV HRC fuse base from the SR60 busbar system % LV HRC fuse base for busbar mounting & LV HRC fuse base, 3P ( LV HRC fuse base, 1P ) LV HRC contact covers * LV HRC fuse link + LV HRC signal detectors , LV HRC partition - LV HRC protective cover LV HRC fuse bases with slewing equipment .

- for screw connection on mounting plate / - for screw connection on busbar system 0 - for claw fixing on busbar 1 LV HRC protective covers for LV HRC fuse bases with slewing equipment 2 LV HRC slewing equipment 3 LV HRC fuse base cover 4 LV HRC isolating link with insulated grip lugs 5 LV HRC isolating link with non-insulated grip lugs 6 LV HRC fuse puller with sleeve 7 LV HRC fuse puller 5 2 3 4 6 7 1 8 9 14 10 11 12 13 15 16 17 18 19 Benefits I2_13743 19 Tripped Not tripped Tripped Not tripped LV HRC fuse links with combination alarm signal the tripping of a fuse by a clear color change from red to white. This en- ables fast identification and replacement of the tripped fuse links.

This increases plant availability. The insulated grip lugs made of metal are integrated in the top and bottom covers of the fuse link in molded plastic and pro- vide greater safety when replacing. The mark shown below in- dicates that the grip lugs are insulated . In the standard series with front indicator, the front-mounted red indicator signals the tripping of a fuse. LV HRC fuse links are always equipped with silver-plated con- tact pins. This means that they are non-corroding and have less contact resistance. This ensures the long-term opera- tional safety of the plant. 19/86 Siemens LV 1 · 2010